Proline Promass E 300 Modbus RS485
Commissioning
Hauser
101
Parameter overview with brief description
Parameter
Description
Selection / User interface /
User entry
Factory setting
Signal mode
Select the signal mode for the double pulse
output.
• Passive
• Active
• Passive NAMUR
–
Master terminal number
Shows the terminal numbers used by the
master of the double pulse output module.
• Not used
• 24-25 (I/O 2)
• 22-23 (I/O 3)
–
Slave terminal number
Shows the terminal numbers used by the
slave of the double pulse output module.
• Not used
• 24-25 (I/O 2)
• 22-23 (I/O 3)
–
Assign pulse output 1
Select process variable for pulse output.
• Off
• Mass flow
• Volume flow
• Corrected volume flow
• Target mass flow
• Carrier mass flow
• Target volume flow
• Carrier volume flow
• Target corrected volume
flow
• Carrier corrected volume
flow
• GSV flow
• GSV flow alternative
• NSV flow
• NSV flow alternative
• S&W volume flow
• Oil mass flow
• Water mass flow
• Oil volume flow
• Water volume flow
• Oil corrected volume flow
• Water corrected volume
flow
–
Measuring mode
Select measuring mode for pulse output.
• Forward flow
• Forward/Reverse flow
• Reverse flow
• Reverse flow compensation
–
Value per pulse
Enter measured value at which a pulse is
output.
Signed floating-point number
Depends on country and
nominal diameter
Pulse width
Define time width of the output pulse.
0.5 to 2
000 ms
–
Failure mode
Define output behavior in alarm condition.
• Actual value
• No pulses
–
Invert output signal
Invert the output signal.
• No
• Yes
–
*
Visibility depends on order options or device settings
10.3.12 Configuring the local display
The
Display
wizard guides you systematically through all the parameters that can
configured for configuring the local display.