PROline Promag 10
11 Description of Device Functions
Hauser
99
11.7
Group PULSE/STATUS OUTPUT
Function description PULSE/STATUS OUTPUT
OPERATION MODE
Use this function to configure the output as a pulse output or status output.
The functions available in this function group vary, depending on which option
you select here.
Options:
OFF
PULSE
STATUS
Factory setting:
PULSE
PULSE VALUE
!
Note!
This function is not available unless the PULSE setting was selected in the
OPERATION MODE function.
Use this function to define the flow at which a pulse is triggered. These pulses
can be totalled by an external totalizer, and the total flow quantity since
measuring started can be registered in this way.
In the SYMMETRY measuring mode (Page 108), the value assigned applies to
both flow directions; in the STANDARD measuring mode it applies only to the
positive flow direction.
User input:
5-digit floating-point number [unit]
Factory setting:
Depends on nominal diameter and country,
[value] [dm
3
...m
3
or US-gal] / pulse;
Corresponds to the factory setting for the pulse value (see Page 116 ff.).
!
Note!
The appropriate unit is taken from the SYSTEM UNITS group (see Page 93).