Unidrive M100 / M101 Control User Guide
67
Issue Number: 1
06.061
Standby Mode Mask
0 to 3
0
RW
Bin
US
06.071
Slow Rectifier Charge Rate
Enable
Off (0) or On (1)
Off (0)
RW
Bit
US
06.073
Braking IGBT Lower Threshold
0 to VM_DC_VOLTAGE_SET V
110 V drive: 390 V
200 V drive: 390 V
400 V drive: 780 V
RW
Num
RA
US
06.074
Braking IGBT Upper Threshold
0 to VM_DC_VOLTAGE_SET V
110 V drive: 390 V
200 V drive: 390 V
400 V drive: 780 V
RW
Num
RA
US
06.075
Low Voltage Braking IGBT
Threshold
0 to VM_DC_VOLTAGE_SET V
0 V
RW
Num
RA
US
06.076
Low Voltage Braking IGBT
Threshold Select
Off (0) or On (1)
Off (0)
RW
Bit
06.077
Low DC Link Operation
Off (0) or On (1)
Off (0)
RW
Bit
US
06.084
UTC Offset
±
24.00 Hours
0.00 Hours
RW
Num
US
06.089
DC Injection Active
Off (0) or On (1)
RO
Bit
NC PT
US
RW
Read / Write
RO
Read only
Num Number parameter
Bit
Bit parameter
Txt Text string
Bin
Binary parameter
FI
Filtered
ND
No default value
NC
Not copied
PT
Protected parameter
RA
Rating dependent
US User save
PS
Power-down save
DE Destination
Date
Date parameter
Time Time parameter
Parameter
Range
(
Ú
)
Default
(
Ö
)
Type
OL
OL
Содержание Unidrive M100