80
Unidrive M100 / M101 Control User Guide
Issue Number: 1
11 Diagnostics
The keypad display on the drive gives various information about the
status of the drive. The keypad display provides information on the
following categories:
•
Trip indications
•
Alarm indications
•
Status indications
11.1 Status modes
Figure 11-1 Keypad status modes
1
Drive OK status
2
Trip
status
3
Alarm
status
11.2 Trip indications
The output of the drive is disabled under any trip condition so that the
drive stops controlling the motor. If the motor is running when the trip
occurs it will coast to a stop.
During a trip condition, the display indicates that a trip has occurred and
the keypad will display the trip string. Some trips have a sub-trip number
to provide additional information about the trip. If a trip has a sub-trip
number, the sub-trip number is flashed alternately with the trip string.
Trips are listed alphabetically in Table 11-2 based on the trip indication
shown on the drive display.
11.3 Identifying a trip / trip source
Some trips only contain a trip string whereas some other trips have a trip
string along with a sub-trip number which provides the user with
additional information about the trip.
A trip can be generated from a control system or from a power system.
The sub-trip number associated with the trips listed in Table 11-1 is in the
form xxyzz
and used to identify the source of the trip.
Table 11-1 Trips associated with xxyzz sub-trip number
The digits xx are 00 for a trip generated by the control system. For a
drive, if the trip is related to the power system then xx will have a value of
01, when displayed the leading zeros are suppressed.
For a control system trip (xx is zero), the y digit where relevant is defined
for each trip. If not relevant, the y digit will have a value of zero.
The zz digits give the reason for the trip and are defined in each trip
description.
Figure 11-2 Key to sub-trip number
Users must not attempt to repair a drive if it is faulty, nor
carry out fault diagnosis other than through the use of the
diagnostic features described in this chapter.
If a drive is faulty, it must be returned to an authorized
Control Techniques distributor for repair.
WARNING
1
3
2
OV
OI.Sn
PSU
PH.Lo
Oht.I
tH.Fb
Oht.P
P.dAt
Oh.dc
x x
y z z
00
-
Generated
by
the
contro
l
modu
l
e
01
-
Generated
by
the
po
w
er
modu
l
e
0
Up
w
ards
- I
dent
i
f
i
es
the
l
ocat
i
on
of
the
tr
i
p
00
01
.
.
07
-
Reason
for
the
tr
i
p