22
Unidrive M100 / M101 Control User Guide
Issue Number: 1
6.2 Menu 0: Basic parameters
* With Unidrive M101, the default is PAd (5).
** Following a rotating autotune Pr
00.009
{05.010} is continuously written by the drive, calculated from the value of
Stator Inductance
(Pr
05.025
). To
manually enter a value into Pr
00.009
{05.010}, Pr
05.025
will need to be set to 0. Refer to the description of Pr
05.010
in the
Parameter Reference
Guide
for further details.
Parameter
Range (
Ú
)
Default (
Ö
)
Type
OL
OL
00.001
Minimum Reference Clamp
{01.007}
VM_NEGATIVE_REF_CLAMP 1 Hz
0.00 Hz
RW Num
US
00.002
Maximum Reference Clamp
{01.006}
VM_POSITIVE_REF_CLAMP Hz
50 Hz default: 50.00 Hz
60 Hz default: 60.00 Hz
RW Num
US
00.003
Acceleration Rate 1
{02.011}
0.0 to VM_ACCEL_RATE s / 100 Hz
5.0
s / 100 Hz
RW Num
US
00.004
Deceleration Rate 1
{02.021}
0.0 to VM_ACCEL_RATE
s / 100 Hz
10.0
s / 100 Hz
RW Num
US
00.005
Drive Configuration
{11.034}
AV (0), AI (1), AV.Pr (2), AI.Pr (3),
PrESEt (4), PAd (5), PAd.rEF (6),
E.Pot (7), torquE (8)
AV (0)
*
RW
Txt
PT
US
00.006
Motor Rated Current
{05.007}
0.00 to VM_RATED_CURRENT A
Maximum Heavy Duty Rating
(11.032) A
RW Num
RA
US
00.007
Motor Rated Speed
{05.008}
0.0 to 33000.0 rpm
50 Hz default:
1500.0 rpm
60 Hz default:
1800.0 rpm
RW Num
US
00.008
Motor Rated Voltage
{05.009}
0 to VM_AC_VOLTAGE_SET V
110 V drive: 230 V
200 V drive: 230 V
400 V drive 50 Hz: 400 V
400 V drive 60 Hz: 460 V
575 V drive: 575 V
690 V drive: 690 V
RW Num
RA
US
00.009
Motor Rated Power Factor
**
{05.010}
0.00 to 1.00
0.85
RW Num
RA
US
00.010
User Security Status
{11.044}
LEVEL.0 (0), ALL (1), r.only.0 (2),
r.only.A (3), Status (4), no.acc (5)
LEVEL.0 (0)
RW Num ND
NC
PT
00.015
Jog Reference
{01.005}
0.00 to 300.00 Hz
1.50 Hz
RW Num
US
00.016
Analog Input 1 Mode
{07.007}
4-20.S (-6), 20-4.S (-5), 4-20.L (-4), 20-4.L (-3),
4-20.H (-2), 20-4.H (-1), 0-20 (0), 20-0 (1),
4-20.tr (2), 20-4.tr (3), 4-20 (4), 20-4 (5), Volt (6)
Volt (6)
RW
Txt
US
00.017
Bipolar Reference Enable
{01.010}
Off (0) or On (1)
Off (0)
RW
Bit
US
00.018
Preset Reference 1
{01.021}
VM_SPEED_FREQ_REF Hz
0.00 Hz
RW Num
US
00.025
User Security Code
{11.030}
0 to 9999
0
RW Num ND
NC
PT
US
00.027
Power-up Keypad Control
Mode Reference
{01.051}
Reset (0), Last (1), Preset (2)
Reset (0)
RW
Txt
US
00.028
Ramp Mode Select
{02.004}
Fast (0), Std (1), Std.bst (2), Fst.bst (3)
Std (1)
RW
Txt
US
00.030
Parameter Cloning
{11.042}
NonE (0), rEAd (1), Prog (2), Auto (3), boot (4)
NonE (0)
RW
Txt
NC
US
00.031
Stop Mode
{06.001}
Coast (0), rp (1), rp.dc I (2), dc I (3),
td.dc I (4),dis (5),
rp (1)
RW
Txt
US
00.032
Dynamic V to F Select
{05.013}
0 to 1
0
RW Num
US
00.033
Catch A Spinning Motor
{06.009}
dis (0), Enable (1), Fr.Only (2),
Rv.Only (3)
dis (0)
RW
Txt
US
00.035
Digital Output 1 Control
{08.091}
0 to 21
0
RW
US
00.037
Maximum Switching
Frequency
{05.018}
0.667 (0), 1 (1), 2 (2), 3 (3), 4 (4),
6 (5), 8 (6), 12 (7), 16 (8) kHz
3 (3) kHz
RW
Txt
US
00.038
Autotune
{05.012}
0 to 2
0
RW Num
NC
US
00.039
Motor Rated Frequency
{05.006}
0.0 to 550.00 Hz
50 Hz: 50.00 Hz
60 Hz: 60.00 Hz
RW Num
RA
US
00.040
Number of Motor Poles
{05.011}
Auto (0) to 32 (16)
Auto 0
RW Num
US
00.041
Control Mode
{05.014}
Ur.S (0), Ur (1), Fd (2), Ur.Auto (3),
Ur.I (4), SrE (5), Fd.tAP (6)
Ur.I (4)
RW
Txt
US
00.042
Low Frequency Voltage Boost
{05.015}
0.0 to 25.0 %
3.0 %
RW Num
US
00.069
Spin Start Boost
{05.040}
0.0 to 10.0
1.0
RW
US
00.076
Action on Trip Detection
{10.037}
0 to 31
0
RW
US
00.077
Maximum Heavy Duty Current
Rating
{11.032}
0.00 to 9999.99 A
RO
Num ND
NC
PT
00.078
Software Version
{11.029}
0 to 999999
RO
ND
NC
PT
00.079
User Drive Mode
{11.031}
OPEn.LP (1)
OPEn.LP (1)
RW
Txt
ND
NC
PT
US
RW Read / Write
RO
Read only
Num Number parameter
Bit
Bit parameter
Txt
Text string
Bin
Binary parameter
FI
Filtered
ND
No default value
NC
Not copied
PT
Protected parameter
RA
Rating dependent
US
User save
PS
Power-down save
DE
Destination
IP
IP address
Mac Mac address
Date Date parameter
Time Time parameter
Содержание Unidrive M100
Страница 100: ...0478 0352 01 ...