Parameter
Range
(
Ú
)
Default
(
Ö
)
Type
OL
OL
06.001
Stop Mode
CoASt (0), rP (1), rP.dc I (2),
dc I (3), td.dc I (4), diS (5)
rP (1)
RW
Txt
US
06.002
Limit Switch Stop Mode
StoP (0) or rP (1),
rP (1)
RW
Txt
US
06.003
Supply Loss Mode
diS (0), rP.StoP (1),
ridE.th (2)
diS (0)
RW
Txt
US
06.004
Start/Stop Logic Select
0 to 6
50 Hz: 0, 60 Hz: 4
RW
Num
US
06.006
Injection Braking Level
0.0 to 150.0 %
100.0 %
RW
Num
RA
US
06.007
Injection Braking Time
0.0 to 100.0 s
1.0 s
RW
Num
US
06.008
Hold Zero Frequency
Off (0) or On (1)
Off (0)
RW
Bit
US
06.009
Catch A Spinning Motor
diS (0), EnAbLE (1),
Fr.OnLy (2), rv.OnLy (3)
diS (0)
RW
Txt
US
06.010
Enable Conditions
0 to 4087
RO
Bin
ND
NC PT
06.011
Sequencer State Machine Inputs
0 to 127
RO
Bin
ND
NC PT
06.012
Enable Stop Key
Off (0) or On (1)
Off (0)
RW
Bit
US
06.014
Disable Auto Reset On Enable
Off (0) or On (1)
Off (0)
RW
Bit
US
06.015
Drive Enable
Off (0) or On (1)
On (1)
RW
Bit
NC
US
06.016
Date
00-00-00 to 31-12-99
RW
Date ND
NC PT
06.017
Time
00:00:00 to 23:59:59
RW
Time ND
NC PT
06.018
Day Of Week
Sun (0), Non (1), tuE (2), UEd (3),
thu (4), Fri (5), SAt (6)
RO
Txt
ND
NC PT
06.019
Date/Time Selector
SEt (0), Po.uP (1), run (2),
Acc.Po (3)
Po.uP (1)
RW
Txt
US
06.020
Date Format
Std (0), US (1)
Std (0)
RW
Txt
US
06.021
Time Between Filter Changes
0 to 30000 Hours
0 Hours
RW
Num
US
06.022
Filter Change Required /
Change Done
Off (0) or On (1)
RW
Bit
ND
NC
06.023
Time Before Filter Change Due
0 to 30000 Hours
RO
Num ND
NC PT
PS
06.024
Reset Energy Meter
Off (0) or On (1)
Off (0)
RW
Bit
06.025
Energy Meter: MWh
±999.9 MWh
RO
Num ND
NC PT
PS
06.026
Energy Meter: kWh
±99.99 kWh
RO
Num ND
NC PT
PS
06.027
Energy Cost Per kWh
0.0 to 600.0
0.0
RW
Num
US
06.028
Running Cost
±32000
RO
Num ND
NC PT
06.029
Hardware Enable
Off (0) or On (1)
RO
Bit
NC
06.030
Run Forward
Off (0) or On (1)
Off (0)
RW
Bit
NC
06.031
Jog Forward
Off (0) or On (1)
Off (0)
RW
Bit
NC
06.032
Run Reverse
Off (0) or On (1)
Off (0)
RW
Bit
NC
06.033
Forward/Reverse
Off (0) or On (1)
Off (0)
RW
Bit
NC
06.034
Run
Off (0) or On (1)
Off (0)
RW
Bit
NC
06.035
Forward Limit Switch
Off (0) or On (1)
Off (0)
RW
Bit
NC
06.036
Reverse Limit Switch
Off (0) or On (1)
Off (0)
RW
Bit
NC
06.037
Jog Reverse
Off (0) or On (1)
Off (0)
RW
Bit
NC
06.038
User Enable
Off (0) or On (1)
Off (0)
RW
Bit
NC
06.039
Not Stop
Off (0) or On (1)
Off (0)
RW
Bit
NC
06.040
Enable Sequencer Latching
Off (0) or On (1)
Off (0)
RW
Bit
US
06.041
Drive Event Flags
0 to 3
0
RW
Bin
NC
06.045
Cooling Fan control
0 to 5
2
RW
Num
US
06.046
Supply Loss Hold Disable
Off (0) or On (1)
Off (0)
RW
Bit
US
06.047
Input Phase Loss Detection
Mode
FuLL (0), rIPPLE (1), diS (2)
FuLL (0)
RW
Txt
US
06.048
Supply Loss Detection Level
0 to VM_SUPPLY_LOSS_LEVEL V
110 V drive: 205 V
200 V drive: 205 V
400 V drive: 410 V
RW
Num
RA
US
06.051
Hold Supply Loss Active
Off (0) or On (1)
Off (0)
RW
Bit
NC
06.052
Motor Pre-heat
Current Magnitude
0 to 100 %
0 %
RW
Num
US
06.058
Output Phase Loss Detection
Time
0.5 (0) to 4 (3) s
0.5 (0) s
RW
Txt
US
06.059
Output Phase Loss Detection
Enable
Off (0) or On (1)
Off (0)
RW
Bit
US
06.060
Standby Mode Enable
Off (0) or On (1)
Off (0)
RW
Bit
US
Содержание Unidrive M100