![Emerson Unidrive M100 Скачать руководство пользователя страница 15](http://html.mh-extra.com/html/emerson/unidrive-m100/unidrive-m100_control-user-manual_2400832015.webp)
Unidrive M100 / M101 Control User Guide
15
Issue Number: 1
9
+24 V user output
Default function
Supply for external digital devices
Voltage tolerance
±20 %
Maximum output current
100 mA
Protection
Current limit and trip
10
Digital I/O 1
Default function
AT ZERO FREQUENCY output
Type
Positive logic digital input, positive logic voltage source output.
PWM or frequency output modes can be selected.
Input / output mode controlled by …
Pr
08.031
Operating as in input
Absolute maximum applied voltage range
-8 V to +30 V relative to 0V
Impedance
6.8 k
Ω
Input threshold
10 V ±0.8 V (IEC 61131-2)
Operating as an output
Nominal maximum output current
50 mA
Maximum output current
100 mA (total inc24 Vout)
Common to all modes
Voltage range
0V to +24 V
Sample rate
1 ms when routed to destinations Pr
06.035
or Pr
06.036
, otherwise 4 ms
11
Digital Input 2
12
Digital Input 3
13
Digital Input 4
Terminal 11 default function
DRIVE ENABLE input
Terminal 12 default function
RUN FORWARD input
Terminal 13 default function
RUN REVERSE input
Type
Positive logic only digital inputs
Voltage range
0V to +24 V
Absolute maximum applied voltage range
-18 V to +30 V relative to 0V
Impedance
6.8 k
Ω
Input threshold
10 V ±0.8 V (IEC 61131-2)
Sample rate
1 ms when routed to destinations Pr
06.035
or Pr
06.036
, otherwise 4 ms.
41
Relay contacts
42
Default function
Drive OK indicator
Contact voltage rating
240 Vac, Installation over-voltage category II
Contact maximum current rating
2 A AC 240 V
4 A DC 30 V resistive load
0.5 A DC 30 V inductive load (L/R = 40 ms)
Contact minimum recommended rating
12 V 100 mA
Contact type
Normally open
Default contact condition
Closed when power applied and drive OK
Update rate
1 ms
To prevent the risk of a fire hazard in the event of a fault, a fuse or other over-current protection must be installed in the relay circuit.
WARNING
Содержание Unidrive M100