9.2.3 Different current ratings
If any of the current rating parameters (Maximum Heavy Duty Rating
(00.077), Maximum Rated Current (11.060) or Full Scale Current Kc
(11.061)) are different between the source and target then all parameters
are still written to the target drive, but some may be limited by their
allowed range. To give similar performance in the target compared to the
source drive the current controller gains are modified as shown below.
Note that this does not apply if the file identification number is larger than
500.
9.2.4 Different variable maximums
It should be noted that if ratings of the source and target drives are
different, it is possible that some parameters with variable maximums
may be limited and not have the same values as in the source drive.
9.2.5 Macro files
Macro files are created in the same way as parameter files except that
NV Media Card Create Special File
(11.072) must be set to 1 before the
file is created on the NV media card.
NV Media Card Create Special File
(11.072) is set to zero after the file has been created or the transfer fails.
When a macro file is transferred to a drive the drive mode is not changed
even if the actual mode is different to that in the file and defaults are not
loaded before the parameters are copied from the file to the drive.
Table 9-1 Functions in Pr mm.000
9.2.6 Writing to the NV Media Card
4yyy - Writes defaults differences to the NV Media Card
The data block only contains the parameter differences from the last
time default settings were loaded.
All parameters except those with the NC (Not copied) coding bit set are
transferred to the NV Media Card.
Writing a parameter set to the NV Media Card (Pr 00.030 =
Prog (2))
Setting Pr
00.030
to Prog (2) and resetting the drive will save the
parameters to the NV Media Card, i.e. this is equivalent to writing 4001
to Pr
mm.000
. All NV Media Card trips apply. If the data block already
exists it is automatically overwritten. When the action is complete this
parameter is automatically reset to NonE (0).
9.2.7 Reading from the NV Media Card
6yyy - Reading from NV Media Card
When the data is transferred back to the drive, using 6yyy in Pr
mm.000
,
it is transferred to the drive RAM and the EEPROM. A parameter save is
not required to retain the data after-power down.
If the data is being transferred to the drive with different voltage or
current rating a
'C.rtg' trip will occur.
The following drive rating dependant parameters (RA coding bit set) will
not be transferred to the destination drive by a NV Media Card when the
voltage rating of the destination drive is different from the source drive
and the file is a parameter file.
However, drive rating dependent parameters will be transferred if only
the current rating is different. If drive rating dependant parameters are
not transferred to the destination drive they will contain their default
values.
Pr
02.008
Standard Ramp Voltage
Pr
04.005
to Pr
04.007
Motoring Current Limits
Pr
04.024
, User Current Maximum Scaling
Pr
04.041
User Over Current Trip Level
Pr
05.007
Rated Current
Pr
05.009
Rated Voltage
Pr
05.010
Rated Power Factor
Pr
05.017
Stator Resistance
Pr
05.018
Maximum Switching Frequency
Pr
05.024
Transient Inductance
Pr
05.025
Stator Inductance
Pr
06.006
Injection Braking Level
Pr
06.048
Supply Loss Detection Level
Pr
06.073
Braking IGBT Lower Threshold
Pr
06.074
Braking IGBT Upper Threshold
Pr
06.075
Low Voltage Braking IGBT Threshold
Reading a parameter set from the NV Media Card (Pr 00.030
= rEAd (1))
Setting Pr
00.030
to rEAd (1) and resetting the drive will transfer the
parameters from the card into the drive parameter set and the drive
EEPROM, i.e. this is equivalent to writing 6001 to Pr
mm.000
.
All NV Media Card trips apply. Once the parameters are successfully
copied this parameter is automatically reset to NonE (0). Parameters are
saved to the drive EEPROM after this action is complete.
9.2.8 Auto saving parameter changes (Pr 00.030 =
Auto (3))
This setting causes the drive to automatically save any changes made to
menu 0 parameters on the drive to the NV Media Card. The latest menu
0 parameter set in the drive is therefore always backed up on the NV
Media Card. Changing Pr
00.030
to Auto (3) and resetting the drive will
immediately save the complete parameter set from the drive to the card,
i.e. all parameters except parameters with the NC coding bit set. Once
the whole parameter set is stored only the individual modified menu 0
parameter setting is updated.
Advanced parameter changes are only saved to the NV Media Card
when Pr
mm.000
is set to 'SAVE' or a 1001 and the drive
Gains
Multiplier
Current Controller Kp Gain
(04.013)
Current Controller Ki Gain
(04.014)
[Source
Full Scale Current Kc
(11.061)] /
[Target
Full Scale Current Kc
(11.061)]
Value
Action
2001
Transfer the drive parameters to parameter file 001 and
sets the block as bootable.
4yyy
Transfer the drive parameters to parameter file yyy.
6yyy
Load the drive parameters from parameter file yyy
7yyy
Erase file yyy.
8yyy
Compare the data in the drive with the file yyy. The data in
the drive is compared to the data in the file yyy. If the files
are the same then Pr
mm.000
is simply reset to 0 when the
compare is complete. If the files are different a {Card
Compare} trip is initiated. All other NV media card trips also
apply.
9555
Clear the warning suppression flag.
9666
Set the warning suppression flag.
9777
Clear the read-only flag.
9888
Set the read-only flag.
Содержание Unidrive M100