84
Unidrive M100 / M101 Control User Guide
Issue Number: 1
dEr.I
Derivative product image error
248
The
dEr.I
trip indicates that an error has been detected in the derivative product image. The reason for the trip can be
identified by the sub-trip number.
Recommended actions:
•
Contact the supplier of the drive
dESt
Two or more parameters are writing to the same destination parameter
199
The
dESt
trip indicates that destination parameters of two or more functions (Menus 7 and 8) within the drive are writing to
the same parameter.
Recommended actions:
•
Set Pr
mm.000
to ‘dest’ or 12001 and check all visible parameters in all menus for parameter write conflicts
dr.CF
Drive configuration
232
The hardware ID does not match the user software ID.
Recommended actions:
Hardware fault – contact the supplier of the drive
Trip
Diagnosis
Sub-trip
Reason
Comments
1
Divide by zero
2
Undefined trip
3
Attempted fast parameter access set-up with non-existent
parameter
4
Attempted access to non-existent parameter
5
Attempted write to read-only parameter
6
Attempted an over-range write
7
Attempted read from write-only parameter
30
The image has failed because either its CRC is incorrect, or
there are less than 6 bytes in the image or the image header
version is less than 5
Occurs when the drive powers-up or the image is
programmed. The image tasks will not run
31
The image requires more RAM for heap and stack than can be
provided by the drive.
As 30
32
The image requires an OS function call that is higher than the
maximum allowed.
As 30
33
The ID code within the image is not valid
As 30
34
The derivative image has been changed for an image with a
different derivative number
As 30
40
The timed task has not completed in time and has been
suspended
Reduce code in timed task or power down repeat
rate
41
Undefined function called, i.e. a function in the host system
vector table that has not been assigned
As 40
51
Core menu customization table CRC check failed
As 30
52
Customizable menu table CRC check failed
As 30
53
Customizable menu table changed
Occurs when the drive powers-up or the image is
programmed and the table has changed. Defaults
are loaded for the derivative menu and the trip will
keep occurring until drive parameters are saved.
80
Image is not compatible with the control board
Initiated from within the image code
81
Image is not compatible with the control board serial number
As 80
Sub-trip
Reason
1
Reserved
2
Invalid hardware ID
3
The hardware ID does not match the user software ID (Size 1-4)