64
Unidrive M100 / M101 Control User Guide
Issue Number: 1
Parameter
Range
(
Ú
)
Default
(
Ö
)
Type
OL
OL
05.001
Output Frequency
VM_SPEED_FREQ_REF Hz
RO
Num
ND NC PT
FI
05.002
Output Voltage
0 to VM_AC_VOLTAGE V
RO
Num
ND NC PT
FI
05.003
Output Power
VM_POWER kW
RO
Num
ND NC PT
FI
05.004
Motor Rpm
±33000 rpm
RO
Num
ND NC PT
FI
05.005
D.C. Bus Voltage
0 to VM_DC_VOLTAGE V
RO
Num
ND NC PT
FI
05.006
Motor Rated Frequency
0.00 to 550.00 Hz
50 Hz: 50.00 Hz,
60 Hz: 60.00 Hz
RW
Num
RA
US
05.007
Motor Rated Current
0.00 to VM_RATED_CURRENT A
Maximum Heavy
Duty Rating (11.032)
RW
Num
RA
US
05.008
Motor Rated Speed
0.0 to 33000.0 rpm
50 Hz: 1500.0 rpm
60 Hz: 1800.0 rpm
RW
Num
US
05.009
Motor Rated Voltage
0 to VM_AC_VOLTAGE_SET V
110V drive: 230 V
200V drive: 230 V
400V drive 50Hz: 400 V
400V drive 60Hz: 460 V
575V drive: 575 V
690V drive: 690 V
RW
Num
RA
US
05.010
Motor Rated Power Factor
0.00 to 1.00
0.85
RW
Num
RA
US
05.011
Number Of Motor Poles
Auto (0) to 32 (16)
Auto (0)
RW
Num
US
05.012
Autotune
0 to 2
0
RW
Num
NC
05.013
Dynamic V To F Select
0 to 1
0
RW
Num
US
05.014
Control Mode
Ur.S (0), Ur (1), Fd (2),
Ur.Auto (3),
Ur.I (4), SrE (5), Fd.tAP (6)
Ur.I (4)
RW
Txt
US
05.015
Low Frequency Voltage Boost
0.0 to 25.0 %
3.0 %
RW
Num
US
05.017
Stator Resistance
0.0000 to 99.9999
Ω
0.0000
Ω
RW
Num
RA
US
05.018
Maximum Switching Frequency
0.667 (0), 1 (1), 2 (2), 3 (3), 4 (4),
6 (5), 8 (6),
12 (7), 16 (8) kHz
3 (3) kHz
RW
Txt
RA
US
05.019
High Stability Space Vector Modulation
Off (0) or On (1)
Off (0)
RW
Bit
US
05.020
Over Modulation Enable
Off (0) or On (1)
Off (0)
RW
Bit
US
05.024
Transient Inductance
0.000 to 500.000 mH
0.000 mH
RW
Num
RA
US
05.025
Stator Inductance
0.00 to 5000.00 mH
0.00 mH
RW
Num
RA
US
05.027
Enable Slip Compensation
±150.0 %
100.0 %
RW
Num
US
05.031
Voltage Controller Gain
1 to 30
1
RW
Num
US
05.033
Slip Compensation Limit
0.00 to 10.00 Hz
10.00 Hz
RW
Num
US
05.035
Auto-switching Frequency Change Disable
0 to 2
0
RW
Num
US
05.036
Slip Compensation Filter
64 (0), 128 (1), 256 (2), 512 (3) ms
128 (1) ms
RW
Txt
US
05.037
Switching Frequency
0.667 (0), 1 (1), 2 (2), 3 (3), 4 (4),
6 (5), 8 (6),
12 (7), 16 (8) kHz
RO
Txt
ND NC PT
05.038
Minimum Switching Frequency
0 to VM_MAX_SWITCHING_
FREQUENCY kHz
0.667 (0) kHz
RW
Txt
RA
05.040
Spin Start Boost
0.0 to 10.0
1.0
RW
Num
US
05.042
Reverse Output Phase Sequence
Off (0) or On (1)
Off (0)
RW
Bit
US
05.059
Maximum Deadtime Compensation
0.000 to 10.000 µs
RO
Num
NC PT
US
05.060
Current At Maximum Deadtime
Compensation
0.00 to 100.00 %
RO
Num
NC PT
US
05.061
Disable Deadtime Compensation
Off (0) or On (1)
Off (0)
RW
Bit
US
05.074
Boost End Voltage
0.0 to 100.0 %
50.0 %
RW
Num
US
05.075
Boost End Frequency
0.0 to 100.0 %
50.0 %
RW
Num
US
05.076
Second Point Voltage
0.0 to 100.0 %
55.0 %
RW
Num
US
05.077
Second Point Frequency
0.0 to 100.0 %
55.0 %
RW
Num
US
05.078
Third point voltage
0.0 to 100.0 %
75.0 %
RW
Num
US
05.079
Third point frequency
0.0 to 100.0 %
75.0 %
RW
Num
US
05.080
Low acoustic noise enable
Off (0) or On (1)
Off (0)
RW
Bit
US
05.081
Change to maximum drive switching
frequency at low output current
Off (0) or On (1)
Off (0)
RW
Bit
US
05.083
Voltage Shelving Disable
Off (0) or On (1)
Off (0)
RW
Bit
US
05.084
Low Frequency Slip Boost
0.0 to 100.0 %
0.0 %
RW
Num
US
05.088
Ur Mode Pre-Flux Delay
0.0 to 0.7 s
0.5 s
RW
Num
US
RW
Read / Write
RO
Read only
Num Number parameter
Bit
Bit parameter
Txt Text string
Bin
Binary parameter
FI
Filtered
ND
No default value
NC
Not copied
PT
Protected parameter
RA
Rating dependent
US User save
PS
Power-down save
DE Destination
Date
Date parameter
Time Time parameter
Содержание Unidrive M100