91
EATON
www.eaton.com
Instruction Booklet
IB020003EN
Effective January 2021
AMPGARD RVSS
Reduced Voltage Soft-Starter
User Manual
Register
Name
Attribute
Description
1061
Protection Overvoltage Alarm Level
UINT16 RW
Units: %
1062
Protection Overvoltage Trip Debounce UINT8 RW
Units: Cycles
1063
Protection Undervoltage Trip Level
UINT8 RW
Units: %
1064
Protection Undervoltage Alarm Level
UINT8 RW
Units: %
1065
Protection Undervoltage Trip
Debounce
UINT16 RW
Units: Cycles
1066
ExternalFault Digital Input NO NC
(Normal Open/Closed)
UINT16 RW
Units: Min
1067
Truck IOC Level
UINT16 RO
Units: %FLA
1068
Truck IOC Debounce Time (cycle)
UINT16 RW
Units: Cycles
1069
Current Foldback Speed (Foldback
Speed)
UINT16 RW
1070
Factory Reset (DSP Param Reset)
UINT8 RW
Units: %
1071
Configurable Pre-Start Check
(PreStart En Word)
UINT8 RW
1072
HW Gain (x10000) (PT Vlt Calib)
UINT16 RW
1073
Low Load Mode On (Transition Type)
UINT8 RW
1074
Bypass Transition Speed (Low Load)
(Ramp Transition Speed)
UINT16 RW
1075
Transition Current Level
UINT16 RW
1076
Protection Jam Trip Level
UINT16 RW
1077
Protection Jam Alarm Level
UINT16 RW
1078
Protection Jam Trip Debounce
UINT8 W
Units: Volts
1079
Backspin Inhibit Time
UINT16 W
Units: %FLA
1080
Time Between Starts
UINT16 RW
Units: Cycles
1081
Transition Run Delay
UINT16 RW
Units: Sec
1082
Motor Cooling Time Constant
UINT16 RW
Units: Sec
1083
RVSS_FLA (Truck Size)
UINT16 RW
Units: Amp
1084
Protection V Unbalance Trip Percent
Level
UINT8 RW
Units: %
1085
Protection V Unbalance Alarm Percent
Level
UINT8 RW
Units: %
1086
Protection V Unbalance Trip
Debounce Time
UINT16 RW
Units: Cycles
1087
Protection I Unbalance Trip Percent
Level
UINT8 RW
Units: %
1088
Protection I Unbalance Alarm Percent
Level
UINT8 RW
Units: %
1089
Protection I Unbalance Trip Debounce
Time
UINT16 RW
Units: Cycles
1090
Truck OverLoad Fault Level
UINT8 RW
Units: %
1091
Truck OverLoad Alarm Level
UINT8 RW
Units: %
1092
Truck OverLoad Debounce
UINT16 RW
Units: Cycles