Instruction Booklet
IB020003EN
Effective January 2021
AMPGARD RVSS
Reduced Voltage Soft-Starter
User Manual
Table 34. Trigger command word - register 802
Code
Command
0
Disable Datalogger
1
Wait For Trigger - Save to Next Memory Block
2
Wait For Trigger - Save to Same Memory Block
3
Wait For Trigger - Save to Memory Block 1
4
Wait For Trigger - Save to Memory Block 2
5
Wait For Trigger - Save to Memory Block 3
6
Wait For Trigger - Save to Memory Block 4
7
Wait For Trigger - Save to Memory Block 5
8
Wait For Trigger - Save to Memory Block 6
9
Wait For Trigger - Save to Memory Block 7
10
Wait For Trigger - Save to Memory Block 8
11
Auto Re-Arm After Reset - Save Next Block
12
Auto Re-Arm After Reset - Save Same Block
Table 35. Datalogger module status - register 435
Code
Command
0
Init_mode
1
Stopped
2
Wait_Trigger
3
Pos_Trigger
4
Triggered
5
Preparing_Buffer
Table 36. Fault disable bitwise - register 1096
Bit
Fault disable (add up decimal enter register
1096)
Decimal
15
Reserved9
32768
14
Reserved10
16384
13
Reserved11
8192
12
Reserved12
4096
11
RVSS Overtemperature
2048
10
LineFreqDev (Undervoltage)
1024
9
LineFreqDev (PLL Phase Error)
512
8
JAM Inst Overcurrent
256
7
Amps Unbalance or 1 Ph
128
6
Voltage Unbalance Or 1Ph
64
5
Overload Truck EOL
32
4
Line FreqDev (FreqOutOfRange)
16
3
Overvoltage
8
2
UnderVoltage
4
1
Motor Overload EOL
2
0
Motor Instantaneous Overcurrent
1
Register 1096 = 0=>All faults enabled
Register 1096=2047=> Faults bit 0 through Bit 10 disabled