Table 26. Motor controller status bits - register 319
BIT
Reason
32
DIN 1: MAIN AUX
31
DIN 2: BYPASS AUX
30
DIN 3: FW RESET
29
DIN 7: CR START/STOP
28
DOUT 1: Ready
27
DOUT 3: CLOSE MAIN
26
DOUT 2: CLOSE BYPASS
25
DOUT 4: FAULTED
24
RTC Needs ReSync
23
DIN 5: Profile Selector
22
DIN 6: Override
21
DOUT 5: UTSD
20
DOUT 6: Current Limit Alarm Active
19
DIN 0: External Fault
18
Start - Ramp
17
Deceleration - Ramp
16
Reserved9
15
Reserved10
14
Reserved11
13
Reserved12
12
Reserved13
11
Reserved14
10
Reserved15
9
Reserved16
8
Reserved17
7
Reserved18
6
Reserved19
5
Reserved20
4
Reserved21
3
Reserved22
2
Reserved23
1
Reserved24
Table 27. Pre-Start fault code - register 332
Code
Fault
0
No Fault
1
Reserved1
2
A-gnd
3
B-gnd
4
C-gnd
5
A-B ph-ph short
6
A-C ph-ph short
7
B-C ph-ph short
8
A SCR short
9
B SCR short
10
C SCR short
11
Reserved2
12
Ph A open
13
Ph B open
14
Ph C open
15
SCR A+ open
16
SCR A- open
17
SCR B+ open
18
SCR B- open
19
SCR C+ open
20
SCR C- open
21
di/dt capacitive fault
22
Unknown OC fault