79
EATON
www.eaton.com
Instruction Booklet
IB020003EN
Effective January 2021
AMPGARD RVSS
Reduced Voltage Soft-Starter
User Manual
5. Soft Start Configuration
1.
Profile 1 Setting
1. Start ramp time
If voltage ramp CL was selected, set time for voltage to ramp from initial to full voltage
3. Kick start voltage
If Kick Start was enabled, set kick start voltage level (different from initial voltage)
4. Kick start time
If Kick Start was enabled, set kick start voltage application time before returning to initial
voltage
5. Initial voltage
If voltage ram CL was selected, set initial voltage for voltage ramp start
6. Current limit
If voltage ramp CL was selected, set maximum motor current allowed during a start
11. Stop ramp time
If
Linear deceleration voltage soft stop was selected, set time for voltage to ramp from
Deceleration initial to Deceleration final voltage
12. Deceleration initial voltage
If
Linear deceleration voltage soft stop was selected, set voltage for initial step down at start
of linear deceleration
13. Deceleration final voltage
If
Linear deceleration voltage soft stop was selected, set output voltage value at which SCRs
switch off and main contactor opens
14. Incomplete sequence time
If voltage ramp CL was selected, set time by which a successful start should have
occurred. Set a time value greater than a typical successful start time, to allow for
temperature differences, but still protect the starter and motor from unusual starting
circumstances.
2.
Profile 2 Setting
1. Start ramp time
5. Initial voltage
6. Current limit
11. Stop ramp time
14. Incomplete sequence time
3. Transition TH%
4. Run Transition Dly
5. Configurable Pre-Start Check
6. Ramp Transition Speed
7. Truck Size
8. Current Foldback Speed
9. Transition Type
inControl Startup Wizard