9.5 Example starter configuration process
The RVSS can be configured using either the MUI or inControl.
Both the MUI and inControl have Startup Wizards and step-by-step
parameter configuration menus. If the RVSS setup only requires
motor data entry and basic system parameters, the Startup Wizards
make the RVSS setup quick and easy.
As it comes from the factory, the RVSS has been configured for the
project-specified motor and power system. During commissioning
it is wise to check the settings. Whenever the BCM is replaced, it
must be completely configured for the target application.
When the inControl application is used, a record copy of as-installed
settings must be made, for factory records. A configuration profile
file can be uploaded from the RVSS, exported through inControl, and
later downloaded to a new BCM if needed.
Configuring the RVSS includes
PRG
menu settings for
• power system parameters,
• control input wiring,
• motor characteristics,
• RVSS operational mode,
• start configuration,
• protections,
• Real Time Clock,
• communications,
• and user interface settings
See
for a summary of RVSS PRG menu parameters.
MUI Starter Configuration
Figure 116. MUI bottom row
,
and OK softkeys and MODE/
BACK button.
MUI operations will involve using MUI softkeys:
• the
MODE/BACK
button to navigate the top menu,
• the
OK
button to make selections,
• the
UP | DN
arrow softkeys (
|
)
to navigate vertically within
the menu,
• the
OK
softkey to choose parameters,
• the
UP | DN
arrow softkeys to increment/decrement parameter
values,
• the
SAVE
softkey to save entries,
• and the
MODE/BACK
button to return to higher-level menus.
Login
When starting from scratch, you may need to log in using the
Administrator password (if one has been set) before entering /
changing RVSS parameters. To log in,
1. Use the Mode | Back button to navigate the MUI LCD top menu
to the
PRG
topic.
2. Use the
|
softkeys to navigate to the
12. Security
topic, click
OK
.
•
|
softkeys to navigate to the
2. Admin PW
topic, click
OK
.
• Click
LOGIN
.
The password field has ten digits, so the password must be entered
right-justified. That is, a six-digit password must start at the fifth digit
from the left, and enter six digits. To navigate to the first password
digit, click the RIGHT arrow softkey (
) to navigate to each digit, the
|
softkeys to enter its numerical value, then the RIGHT arrow
softkey to navigate to the next digit. When finished, click
LOGIN
. If
successful, you will see a
Logged in
message. Click the Mode | Back
button to return to
12. Security
, then Mode | Back to return to the
PRG