Instruction Booklet
IB020003EN
Effective January 2021
AMPGARD RVSS
Reduced Voltage Soft-Starter
User Manual
Topic
Parameter
Units
Description
Starter Profile
Used to select the desired control profile
0 = None.
1 = Voltage Ramp CL
10 = Current ramp
11 = Pump Acceleration
12 = Voltage Ramp CL & SAG
13 = Jog forward
14 =Jog reverse
Stop Profile
Used to select the desired control profile
0 = Coast Stop
1 = Linear Deceleration Ramp Down
10 = Pump Deceleration
Kick Start Enable
Kick Start Enable Profile 1
0 = Disable
1 = Enable
Starter Profile
Used to select the desired control profile
0 = None.
1 = Voltage Ramp CL
10 = Current ramp
11 = Pump Acceleration
12 = Voltage Ramp CL & SAG
13 = Jog forward
14 =Jog reverse
Stop Profile
Used to select the desired control profile
0 = Coast Stop
1 = Linear Deceleration Ramp Down
10 = Pump Deceleration
Kick Start Enable
Kick Start Enable Profile 1
0 = Disable
1 = Enable
Run Transition
Settings
Transition Threshold Percent
Motor Transition to Run Threshold Percent
Run Transition Delay
If the motor is instructed to run by the user, but the current thresholds are not
reached, the C445 will not fault on Undercurrent if that protection is enabled
because it has not realized a run state. If the user wants the unit to fault under these
conditions on an enabled protection following the selected debounce time for that
protection, a time must be selected for this parameter (in seconds).
Configurable Pre-Start Check
Configurable Pre-Start Check (parameter, see
XXX
Ramp Transition Speed
Ramp Transition Speed (in RPM)
Transition Type
Transition Type
0 = Full Voltage
1 = Ramp Up
Current Foldback Speed
Current Foldback Speed (RPM)
Truck Size
Truck Size
0 = FOUR HUNDRED AMPS
1 = EIGHT HUNDRED AMPS
Profile 1
Settings