90
EATON
www.eaton.com
Instruction Booklet
IB020003EN
Effective January 2021
AMPGARD RVSS
Reduced Voltage Soft-Starter
User Manual
Register
Name
Attribute
Description
1028
Deceleration Initial Voltage Profile 1
UINT16 RW
Units: %
1029
Deceleration Final Voltage Profile 1
UINT16 RW
Units: %
1030
Kick Start Enable Profile 1
BYTE RW
1031
Kick Start Voltage Profile 1
UINT16 RW
Units: %
1032
Kick Start Time Profile 1
UINT16 RW
Units: Cycles
1033
Rvss Start Type Profile 2
WORD RW
1034
Rvss Decel Type Profile 2
WORD RW
1035
Voltage Sag Limit Profile 2
UINT16 RW
Units: %
1036
Start Ramp Time Profile 2
UINT16 RW
Units: Sec
1037
Jog Voltage Profile 2
UINT16 RW
Units: %
1038
Initial Current Profile 2
UINT16 RW
Units: %
1039
Initial Voltage Profile 2
UINT16 RW
Units: %
1040
Current Limit Profile 2
UINT16 RW
Units: %
1041
Max Current Profile 2
UINT16 RW
Units: %
1042
Stop Ramp Time Profile 2
UINT16 RW
Units: Sec
1043
Deceleration Initial Voltage Profile 2
UINT16 RW
Units: %
1044
Deceleration Final Voltage Profile 2
UINT16 RW
Units: %
1045
Kick Start Enable Profile 2
BYTE RW
1046
Kick Start Voltage Profile 2
UINT16 RW
Units: %
1047
Kick Start Time Profile 2
UINT16 RW
Units: Cycles
1048
Incomplete Sequence Time Profile 1
UINT16 RW
Units: Sec
1049
Incomplete Sequence Time Profile 2
UINT16 RW
Units: Sec
1050
Number Of Starts Per Hour Allowed
Before Trip
UINT16 RW
1051
Phase Order (User Select
/Abc/Acb)
UINT8 RW
1052
Motor Overload Trip Level
UINT8 RW
Units: %
1053
Motor Overload Alarm Level
UINT8 RW
Units: %
1054
Locked Rotor Time
UINT16 RW
Units: Sec
(O/L Class Overload Curve or Time)
1055
Locked Rotor Current
UINT16 RW
Units: %FLA
1056
Protection Instantaneous Overcurrent
Trip Level
UINT16 RW
Units: %
Motor Overcurrent level
1058
Protection Instantaneous Overcurrent
Debounce
UINT8 RW
Units: Cycles
1059
Enable_PreCheck_Test
UINT8 RW
1060
Protection Overvoltage Trip Level
UINT16 RW
Units: %