AMPGARD RVSS
Reduced Voltage Soft-Starter
User Manual
Figure 35.
Device and Motor Status
Color
-Red = Fault
- Yellow = Warning
-Green = No Fault/Warning
Flash Rate
-Mostly ON = Actively polled >1s poll rate (any protocol)
- Mostly OFF = Not being polled from the network
CH1 & CH2 Status
- Green/Rapid (50ms ON/50ms OFF) = Device Discovery
Modbus Status
USB Status
Color green = indication of traffic
Color green = indication of traffic
- Green/Mostly ON (1.45s ON/50ms OFF) = Device connected,
data being exchanged
- Green/Mostly OFF (50ms ON/1.45s OFF) = Device
connected, no data being exchanged
- Red/Slow (1s ON/1s OFF) = Connected device missing or
damaged
Ethernet module Network Status (NS)
and Module Status (MS)
BCM LED status indications.
Table 6. Ethernet card module status (MS) indicator
Indicator state
Summary
Requirement
Steady off
No power
If no power is supplied to device, the module status indicator shall be steady Off.
Steady green
Device operational
If the device is operating correctly, the module status indicator shall be steady green
Flashing green
Standby
If the device has not been configured, the module status indicator shall be flashing green.
Flashing red
Minor fault
If the device has detected a recoverable minor fault, the module status indicator shall be flashing red.
Steady red
Major fault
f the device has detected a non-recoverable major fault, the module status indicator shall be steady red.
Table 7. Ethernet card network status (NS) indicator
Indicator state
Summary
Requirement
Steady off
Not powered, no IP
address
The device is powered off, or is powered on but with no IP address configured (Interface Configuration attribute of the TCP/
IP Interface Object).
Steady green
No connections
An IP address is configured, but no CIP connections are established, and an Exclusive Owner connection has not timed out.
Flashing red
Connection time-
out
An Exclusive Owner connection for which this device is the target has timed out. The network status indicator shall return to
steady green only when all timed out Exclusive Owner connections are re-established.
Steady red
Duplicate IP
f the device has detected a non-recoverable major fault, the module status indicator shall be steady red.
Flashing green and red
Self-test
While the device is performing its power up testing, the module status indicator shall be flashing green and red.
6.7.3 Monitoring user interface (MUI)
This door-mounted module (see
and
) provides
advanced local monitoring, parameter editing, complete fault data
and optional local control.