Products information ErP
AQUATOP T14C(R)-T07CHT-T11CHT-T17C(R
Type
AQUATOP
Model
T14C
T07CHT T11CHT T17CH
Air-to-water heat pump
No
No
No
No
Water-to-water heat pump
Yes
Yes
Yes
Yes
Brine-to-water heat pump
Yes
Yes
Yes
Yes
Low temperature heat pump
No
No
No
No
Equipped with a supplementary heater:
Yes
Yes
Yes
Yes
Heat pump combination heater
No
No
No
No
Item
Simbolo Unità
Value
Value
Value
Value
Rated heat output
Prated
[kW]
13
7
10
17
Declared capacity for heating for part load at indoor temperature 20 °C and outdoor temperature Tj / W45
Tj= -7°C
Pdh
[kW]
13.7
6.9
9.9
17.5
Tj= +2°C
Pdh
[kW]
7.3
10.5
14.4
18.4
Tj= +12°C
Pdh
[kW]
7.7
11.1
15.3
19.5
Tj = bivalent temperature
Pdh
[kW]
6.8
9.8
13.5
17.2
Tj = operation limit temperature
Pdh
[kW]
6.8
9.8
13.5
17.2
Bivalent temperature
Tbiv
[°C]
-10
-10
-10
-10
Cycling interval capacity for heating
Pcych
[kW]
6.8
9.8
13.5
17.2
Degradation coefficient
Cdh
1.0
1.0
1.0
1.0
Power consumption in modes other than active mode
Off mode
Poff
[kW]
0.000
0.000
0.000
0.000
Thermostat-off mode
PTO
[kW]
0.010
0.010
0.010
0.010
Standby mode
PSB
[kW]
0.010
0.010
0.010
0.010
Crankcase heater mode
PCK
[kW]
0.000
0.000
0.000
0.000
Other items
Capacity control
Fix
Fix
Fix
Fix
Sound power level, indoors/ outdoors
L
WA
[dBA]
51
48
49
48
Seasonal space heating energy efficiency
η
s
%
173
162
170
176
Fix
Information products according to Directive 2009/125 / EC
71