![elco AQUATOP T Series Скачать руководство пользователя страница 69](http://html1.mh-extra.com/html/elco/aquatop-t-series/aquatop-t-series_operating-instructions-manual_2377146069.webp)
Products information ErP
AQUATOP T05C(R,X)-T12C(R,X)
Type
AQUATOP
Model
T05C
T06C
T08C
T10C
T12C
Air-to-water heat pump
No
No
No
No
No
Water-to-water heat pump
Yes
Yes
Yes
Yes
Yes
Brine-to-water heat pump
Yes
Yes
Yes
Yes
Yes
Low temperature heat pump
No
No
No
No
No
Equipped with a supplementary heater:
Yes
Yes
Yes
Yes
Yes
Heat pump combination heater
No
No
No
No
No
Item
Symbol Unit
Value
Value
Value
Value
Value
Rated heat output
Prated
[kW]
5
7
8
9
11
Declared capacity for heating for part load at indoor temperature 20 °C and outdoor temperature Tj / W45
Tj= -7°C
Pdh
[kW]
5.1
6.6
7.8
9.2
11.4
Tj= +2°C
Pdh
[kW]
5.4
7.0
8.2
9.7
12.0
Tj= +12°C
Pdh
[kW]
5.7
7.4
8.7
10.2
12.7
Tj = bivalent temperature
Pdh
[kW]
5.0
6.5
7.7
9.0
11.2
Tj = operation limit temperature
Pdh
[kW]
5.0
6.5
7.7
9.0
11.2
Bivalent temperature
Tbiv
[°C]
-10
-10
-10
-10
-10
Cycling interval capacity for heating
Pcych
[kW]
5.0
6.5
7.7
9.0
11.2
Degradation coefficient
Cdh
1.0
1.0
1.0
1.0
1.0
Power consumption in modes other than active mode
Off mode
Poff
[kW]
0.000
0.000
0.000
0.000
0.000
Thermostat-off mode
PTO
[kW]
0.010
0.010
0.010
0.010
0.010
Standby mode
PSB
[kW]
0.010
0.010
0.010
0.010
0.010
Crankcase heater mode
PCK
[kW]
0.000
0.000
0.000
0.000
0.000
Other items
Capacity control
Fix
Fix
Fix
Fix
Fix
Sound power level, indoors/ outdoors
L
WA
[dBA]
47
47
49
49
49
Seasonal space heating energy efficiency
η
s
%
163
164
167
168
174
Information products according to Directive 2009/125 / EC
69