61
Technical Data
AQUATOP T10CRX-T12CRX
Heat Pump Type AQUATOP T...CR
T10CRX
T12CRX
Usage Range
Heat source brine outlet
Tmin
°C
-5
-5
Heat source water outlet
Tmin
°C
3
3
Heater flow temperature
min/max
°C
20/55
20/55
Electrical Data
Operating voltage, feed
1 x 230 V / 50 Hz
Rated input with B0/W35
PNT
kW
2.2
2.8
Ext. protection with electric heating element
AT
32
32
Ext. protection without electric heating element
AT
32
32
Rated current electric heating element
l max
A
9
9
Rated current compressor
I max.
A
23.1
23.5
Current with blocked rotor
LRA
A
100
114
Starting current with soft starter
VSA
A
45
45
Power consumption el. heating element
Pmax.
kW
6/4/2
Power consumption circulating pumps
Pmax.
kW
0.25
0.45
Starts per hour
max.
(-)
3
3
Start delay after power outage
sec.
60-120
Dimensions / Connections / Misc.
Weight
kg
204
203
Dimensions
WxDxH
mm
670x950x1050
Heating circuit connection
fem. thrd.
inch
1"
1"
Brine circuit connection
fem. thrd.
inch
1"
1"
Sound power level
Lwa
dB(A)
43
45
Sound power level at distance of 5 m
2)
Lpa
dB(A)
25
27
Expansion vessel heater
V
l
12
12
Set default pressure heating circuit
p
bar
1
1
Expansion vessel brine circuit
V
l
12
12
Set default pressure brine circuit
p
bar
1
1
Safety valve (brine/heater)
p
bar
3
3
LP pressure controller OFF- switch off
p
bar
1.5
1.5
LP pressure controller ON- switch on
p
bar
2.9
2.9
HP pressure controller OFF- switch off
p
bar
29
29
HP pressure controller ON- switch on
p
bar
24
24
Switching point brine pressure monitor
p
bar
Off 0.65 / On 0.80
1) In accordance with EN14511. The standard data and volumetric flow rates of the water heat pumps corresponds
to the standard model
2) Incl. circulating pump
3) Required length of the geothermal probe for normal geological conditions (45 W/m), without hot water heating.
4) Residual delivery pressure is indicated at highest level
5) Water/ethylene glycol: cp=~3.6 [KJ/kg*K], p=~1.05 [kg/dm3] (ASHRAE)
6)
∆
T max= 10 K, for PWW production
∆
Tmax = 5 K. (V' [l/h]= Qh[kW]/(4.18*
∆
T[K]*p[kg/l])* 3600)