![elco AQUATOP T Series Скачать руководство пользователя страница 51](http://html1.mh-extra.com/html/elco/aquatop-t-series/aquatop-t-series_operating-instructions-manual_2377146051.webp)
51
Technical Data
AQUATOP T05CX - T08CX (available in F/I/B)
Heat Pump Type AQUATOP T...CX
T05CX
T06CX
T08CX
Electrical Data
Operating voltage, feed
1 x 230 V / 50 Hz
Rated input with B0/W35
PNT
kW
1.2
1.5
1.9
Ext. protection with electric heating element
AT
32
32
32
Ext. protection without electric heating element
AT
16
20
25
Rated current electric heating element
I max
A
9
9
9
Rated current compressor
I max.
A
11.4
14.8
17.3
Current with blocked rotor (LRA)
LRA
A
47
61
76
Starting current with soft starter
VSA
A
45
45
45
Power consumption el. heating element
max.
kW
6/4/2
Power consumption circulating pumps
max.
kW
0.13
0.13
0.25
Starts per hour
max.
(-)
3
3
3
Start delay after power outage
sec.
60-120
Dimensions / Connections / Misc.
Weight
kg
185
190
196
Dimensions
WxDxH
mm
670x950x1050
Heating circuit connection
fem. thrd.
inch
1"
1"
1"
Brine circuit connection
fem. thrd.
inch
1"
1"
1"
Sound power level
Lwa
dB(A)
41
41
41
Expansion vessel heater
V
l
12
12
12
Set default pressure heating circuit
p
bar
1
1
1
Expansion vessel brine circuit
V
l
12
12
12
Set default pressure brine circuit
p
bar
1
1
1
Safety valve (brine/heater)
p
bar
3
3
3
Switching point brine pressure monitor
p
bar
Off 0.65 / On 0.80
LP pressure controller OFF- switch off
p
bar
1.5
1.5
1.5
LP pressure controller ON- switch on
p
bar
2.9
2.9
2.9
HP pressure controller OFF- switch off
p
bar
29
29
29
HP pressure controller ON- switch on
p
bar
24
24
24
1) In accordance with EN14511
2) Incl. circulating pump
3) Required length of the geothermal probe for normal geological conditions (45 W/m), without hot water heating.
4) Residual delivery pressure is indicated at highest level
5) Water/ethylene glycol: cp=~3.6 [KJ/kg*K], p=~1.05 [kg/dm3] (ASHRAE)
6)
∆
T max= 10 K, for PWW production
∆
Tmax = 5 K. (V' [l/h]= Qh[kW]/(4.18*
∆
T[K]*p[kg/l])*3600)