45
Technical Data
AQUATOP T07CHT - T11CHT
Heat Pump AQUATOP T
T07CHT
T11CHT
Electrical Data
Operating voltage, feed
3 x 400 V / 50 Hz
Rated input with B0/W35
PNT
kW
1.6
2.3
Ext. protection with electric heating element
AT
20
25
Ext. protection without electric heating element
AT
16
20
Rated current electric heating element
l max.
A
9
9
Rated current compressor
I max.
A
10
13
Current with blocked rotor
LRA
A
50
74
Starting current with soft starter
VSA
A
25
32.5
Power consumption el. heating element
Pmax.
kW
6/4/2
Power consumption circulating pumps
Pmax.
kW
0.22
0.23
Starts per hour
max.
(-)
3
3
Start delay after power outage
sec.
60-120
Dimensions / Connections / Misc.
Weight
kg
203
221
Dimensions
WxDxH
mm
670x950x1050
Heating circuit connection
fem. thrd.
inch
1"
1"
Brine circuit connection
fem. thrd.
inch
1"
1"
Sound power level
Lwa
dB(A)
45
49
Expansion vessel heater
V
l
12
12
Primary pressure heating circuit expansion vessel
p
bar
1
1
Expansion vessel brine circuit
V
l
12
2 x 12
Primary pressure brine circuit expansion vessel
p
bar
1
1
Safety valve (brine/heater)
p
bar
3
3
Switching point brine pressure monitor
p
bar
Off 0.65 / On 0.80
LP pressure controller OFF- switch off
p
bar
0.9
0.9
LP pressure controller ON- switch on
p
bar
2
2
HP pressure controller OFF- switch off
p
bar
20
20
HP pressure controller ON- switch on
p
bar
16
16
1) In accordance with EN14511 (*measured at Heat Pump Testing Center)
2) Incl. circulating pump
3) Required length of the geothermal probe for normal geological conditions (45 W/m), without hot water heating.
4) Residual delivery pressure is indicated at highest level
5) Water/ethylene glycol: cp=~3.6 [KJ/kg*K], p=~1.05 [kg/dm3] (ASHRAE)
6)
∆
T max= 10 K, for PWW production
∆
Tmax = 5 K. (V' [l/h]= Qh[kW]/(4.18*
∆
T[K]*p[kg/l])*3600)
7) At nominal volume flow