5.13 Setpoint toggle (day / night operation)
Controller setpoints can be entered double as a standard value and an alternative value. Setpoint toggle allows
changing between these two values. Setpoint toggling can be made in two ways:
External
: By voltage applied to 230 V- Digital Input 2 (Terminal D21/D22, factory setting) by a switch or
timer. Alternatively, with an appropriate parameterization of the digital inputs (menu 6-2-4), the setpoint
switch can be carried out via digital input 1 (terminals D11/D12) or digital input 4 (terminals D41/D42). The
function of the digital inputs can be configured via the parameters Inv.
D1 to Inv.
D4 (menu 6-2-4). If more
than one input has been parameterized with the same function, then this function is active as soon as a
signal is applied to one of these inputs.
Internal
: By setting toggle times on the internal clock. (only active when the parameter
Toggle interv.
(Menu
3-3) is set to "--").
CAN bus
: With the use of a system centre or a suitable store computer (version 4.24 or higher) he setpoint
can also be controlled from the system centre / store computer via CAN bus. Further information on setpoint
switching can be found in the system centre's / store computer's documentation in the chapter "Special
Inputs".
UA 111, UA 111 D, UA 121:
The fan stops for an adjustable time (night blind close time). The fan restarts when toggling back from
alternative to standard setpoints.
Night blind run time
UA 141, UR 141 TK (LT), UR 141 NK (NT)
Warning - hazardous electrical voltage!
Danger of electric shock! BEFORE
connecting and disconnecting it must be checked that the 230
V AC digital inputs are
off load
! The controller and connected voltage carrying components remain
supplied with power!
Night blind close time
As a rule, the night blind is closed on refrigerated multidecks when toggling
setpoints. Some cases require the fans to be stopped while the night blind is being closed to prevent it
from being forced out of the case.
Setpoint toggle can be activated via digital Input 2 (terminals D21 and D22). This requires digital Input
2 to be set as SETP.TOGGLE (Menu 6-2-4) for external setpoint toggle to be available.
Содержание UA 400
Страница 26: ...Firmware V3 15 21 04 2021 26 401 Solenoid valve Relay for Solenoid Valve 1...
Страница 133: ...Firmware V3 15 21 04 2021 133 401 Upper case and lower case can be toggled by tapping the MODE button...
Страница 172: ...Firmware V3 15 21 04 2021 172 401 Service Mode 6 7 2 SERVICE MOD...
Страница 244: ...Firmware V3 15 21 04 2021 244 401...
Страница 324: ...Firmware V3 15 21 04 2021 324 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint...
Страница 357: ...Firmware V3 15 21 04 2021 357 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint...
Страница 361: ...Firmware V3 15 21 04 2021 361 401 FANS 2 Pos XXXXX Fan Delay Fan delay...
Страница 372: ...Firmware V3 15 21 04 2021 372 401...
Страница 399: ...Firmware V3 15 21 04 2021 399 401 12 2 Mechanical Data DIN rail mounting A Connector set with cable All dimensions in mm...