6.5 Battery replacement
Only UA 400 AC
The case controller has a buffer battery of the
type CR 2450 N, 3 V Lithium
. In order to change the battery, it is
necessary to remove the case controller from the system. In this case, the refrigeration point is
not
regulated
and monitored!
Performing the battery replacement
Disconnect case controller and refrigeration point from the power supply. Acknowledge alarm in the higher
level controller if necessary.
Disconnect all plug connectors, remove the device from the DIN rail.
(A)
Push the plastic lid’s two left-hand snap lugs on the side upwards with a broad flat blade screwdriver
and
(B)
lift up the lid with a swivelling movement.
•
•
•
DANGER
Warning about dangerous electrical voltage! Danger of electric shock!
The safety regulations
and work safety instructions in chapter
must be observed for the battery replacement.
A battery replacement may
only
be performed by trained personnel or at the factory by the
manufacturer!
All
plug connectors may only be inserted and removed when the
power supply is disconnected
.
Label connector if necessary before the removal and then detach.
Circuit boards may only be replaced when the
power supply is disconnected
. Always hold circuit
boards at the edge.
Observe ESD (Electrostatic Discharge) regulations (see manual
)!
Risk of false alarm!
The removal of the controller from the CAN bus generates an error message in
the higher level controller (
). Therefore, in addition to the precautionary measures that
directly affect the control, consequences on the higher level controllers connected to the CAN bus
must also be considered.
level controller and that the service centre has previously been informed accordingly.
Warning about dangerous electrical voltage! Danger of electric shock!
A voltage of 230 V AC
can be present on some connectors.
Содержание UA 400
Страница 26: ...Firmware V3 15 21 04 2021 26 401 Solenoid valve Relay for Solenoid Valve 1...
Страница 133: ...Firmware V3 15 21 04 2021 133 401 Upper case and lower case can be toggled by tapping the MODE button...
Страница 172: ...Firmware V3 15 21 04 2021 172 401 Service Mode 6 7 2 SERVICE MOD...
Страница 244: ...Firmware V3 15 21 04 2021 244 401...
Страница 324: ...Firmware V3 15 21 04 2021 324 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint...
Страница 357: ...Firmware V3 15 21 04 2021 357 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint...
Страница 361: ...Firmware V3 15 21 04 2021 361 401 FANS 2 Pos XXXXX Fan Delay Fan delay...
Страница 372: ...Firmware V3 15 21 04 2021 372 401...
Страница 399: ...Firmware V3 15 21 04 2021 399 401 12 2 Mechanical Data DIN rail mounting A Connector set with cable All dimensions in mm...