Menu 6-2-3 Alarm Delay
ALARMDELAY POS: XXXXX
Entry
Default
Sensor Fault XX m
Sensor break alarm delay
0..30
15 min
High/Low Temp. XX m
High/low temperature alarm delay
0..150
90 min
Door Open XX m
Cold-room door open alarm delay
0 .. 60
60 m
No Defrost XX h
No defrost alarm delay
--, 2..168
30 h
Selfholding X
NO: Automatic reset of non- transient alarms.
YES: Alarms must be reset manually.
,
, (Y/N)
N
Menu 6-2-4 230V Inputs
230V INPUT POS: XXXXX
Entry
Default
Entry1: XXXXXXXXXX
Function of digital input 1 D11/D12
1)
DEFR.TIMER
Entry2: XXXXXXXXXX
Function of digital input 2 D21/D22
2)
DOOR CONTACT
Entry3: XXXXXXXXXX
Function of digital input 3 D31/D32
3)
DOOR CONTACT
Entry4: XXXXXXXXXX
Function of digital input 4 D41/D42
4)
Extern.Alarm
XXXXXXXXXXXXXXXXXXX
Freely configurable alarm text for digital input
4,the default text is "CO2-Alarm"
Text
CO2-ALARM
Inv. D1 XXX
Inverting of digital input 1
,
, (ON/OFF)
OFF
Inv. D2 XXX
Inverting of digital input 2
OFF
Inv. D3 XXX
Inverting of digital input 3
OFF
Inv. D4 XXX
Inverting of digital input 4
OFF
Possible settings for the digital inputs:
DEFR.TIMER Defrost timer*
MANUAL OFF. Manual shutoff both zones
MANUAL OFF. Z1 Manual shutoff only Z1
MANUAL OFF. Z2 Manual shutoff only Z2
TOGGLE SETP. Toggle setpoint
DOOR CONTACT Door contact 2 *
MANUAL OFF Manual shutoff both zones
MANUAL OFF. Z1 Manual shutoff only Z1
MANUAL OFF. Z2 Manual shutoff only Z2
TOGGLE SETP Toggle setpoint
DOOR CONTACT Door contact 1 *
MANUAL OFF Manual shutoff both zones *
MANUAL OFF. Z1 Manual shutoff only Z1
MANUAL OFF. Z2 Manual shutoff only Z2
Only trained personnel should be allowed to change inputs, as changes may affect other functions.
Содержание UA 400
Страница 26: ...Firmware V3 15 21 04 2021 26 401 Solenoid valve Relay for Solenoid Valve 1...
Страница 133: ...Firmware V3 15 21 04 2021 133 401 Upper case and lower case can be toggled by tapping the MODE button...
Страница 172: ...Firmware V3 15 21 04 2021 172 401 Service Mode 6 7 2 SERVICE MOD...
Страница 244: ...Firmware V3 15 21 04 2021 244 401...
Страница 324: ...Firmware V3 15 21 04 2021 324 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint...
Страница 357: ...Firmware V3 15 21 04 2021 357 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint...
Страница 361: ...Firmware V3 15 21 04 2021 361 401 FANS 2 Pos XXXXX Fan Delay Fan delay...
Страница 372: ...Firmware V3 15 21 04 2021 372 401...
Страница 399: ...Firmware V3 15 21 04 2021 399 401 12 2 Mechanical Data DIN rail mounting A Connector set with cable All dimensions in mm...