Firmware V3.15
21.04.2021
54/401
2. Operating mode "flow"
The fan relay is switched on continuously during the cooling in this operating mode.
The fan relay switches off at the start of a defrost. The fan relay switches on if the parameter
Lüfter Über
at the
evaporator sensor is exceeded. When the defrost is complete, the fan relay Is switched on again in all cases.
Only the evaporator sensor R1.1 is used for fan control in single-zone operation.
Both evaporator sensors R1.1
and
R1.3 are used for fan control in two-zone operation. If the evaporator sensor
R1.3 is not attached, then only the evaporator sensor R1.1 is also used for fan control in two-zone operation.
The two parameters
Lüfteranlauf
and
Lüfter Über
have no effect in this operating mode.
The fan relay does not change its state during any possibly parametrised drip time. The
parameter
Lüfter Über
is already evaluated during a possibly parametrised wait time. The
parameter
Lüfterverzöger
has no effect in this operating mode.
Содержание UA 400
Страница 26: ...Firmware V3 15 21 04 2021 26 401 Solenoid valve Relay for Solenoid Valve 1...
Страница 133: ...Firmware V3 15 21 04 2021 133 401 Upper case and lower case can be toggled by tapping the MODE button...
Страница 172: ...Firmware V3 15 21 04 2021 172 401 Service Mode 6 7 2 SERVICE MOD...
Страница 244: ...Firmware V3 15 21 04 2021 244 401...
Страница 324: ...Firmware V3 15 21 04 2021 324 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint...
Страница 357: ...Firmware V3 15 21 04 2021 357 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint...
Страница 361: ...Firmware V3 15 21 04 2021 361 401 FANS 2 Pos XXXXX Fan Delay Fan delay...
Страница 372: ...Firmware V3 15 21 04 2021 372 401...
Страница 399: ...Firmware V3 15 21 04 2021 399 401 12 2 Mechanical Data DIN rail mounting A Connector set with cable All dimensions in mm...