9.2.3 Menu 2 Setpoints UA 111 D
SETPOINTS POS: XXXXX
1 Cooling
Move to menu 2-1 Special case: Move to menu 2-1-1 when single-zone operation is
set (Menu 6-1) and setpoint toggle is disabled (Menu 3-3).
2 Defrost
Move to menu 2-2 Special case: Move to menu 2-2-1 when single-zone operation is
set (Menu 6-1) and setpoint toggle is disabled (Menu 3-3).
3
Not used with this controller type
4 Alarm
Move to menu 2-4 Special case: Move to menu 2-4-1 when single-zone operation is
set (Menu 6-1) and setpoint toggle is disabled (Menu 3-3).
5 Frame Heater
Move to menu 2-5
Menu 2-1 Cooling
COOLING POS: XXXXX
1 Zone 1
Menu 2-1-1
2
Not used with this controller type
3 Zone 1A Altern.
Menu 2-1-3
Not shown when setpoint toggle is disabled (Menu 3-3)
Menu 2-1-1 Zone 1
COOLING 1 POS: XXXXX
Entry
Default
Setpoint R2.x XXX °C
Supply air temperature setpoint
-10..20
-2 °C
Hystersis R2.x X K
Supply air temperature hysteresis setpoint
1..8
4 K
Setpoint R4.x XXX °C
Return air temperature setpoint for comparison
-4..20
5 °C
Hystersis R4.x X K
Return air temperature hysteresis setpoint
1..8
2 K
Menu 2-1-2
Not used with this controller type
Menu 2-1-3 Zone 1A Altern.
COOLING 1A POS: XXXXX
Entry
Default
Setpoint R2.x XXX °C
Supply air temperature setpoint
-10..20
0 °C
Hystersis R2.x X K
Supply air temperature hysteresis setpoint
1..8
4 K
Setpoint R4.x XXX °C
Return air temperature setpoint for comparison
-4..20
5 °C
Hystersis R4.x X K
Return air temperature hysteresis setpoint
1..8
2 K
Menu 2-2 Defrost
Содержание UA 400
Страница 26: ...Firmware V3 15 21 04 2021 26 401 Solenoid valve Relay for Solenoid Valve 1...
Страница 133: ...Firmware V3 15 21 04 2021 133 401 Upper case and lower case can be toggled by tapping the MODE button...
Страница 172: ...Firmware V3 15 21 04 2021 172 401 Service Mode 6 7 2 SERVICE MOD...
Страница 244: ...Firmware V3 15 21 04 2021 244 401...
Страница 324: ...Firmware V3 15 21 04 2021 324 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint...
Страница 357: ...Firmware V3 15 21 04 2021 357 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint...
Страница 361: ...Firmware V3 15 21 04 2021 361 401 FANS 2 Pos XXXXX Fan Delay Fan delay...
Страница 372: ...Firmware V3 15 21 04 2021 372 401...
Страница 399: ...Firmware V3 15 21 04 2021 399 401 12 2 Mechanical Data DIN rail mounting A Connector set with cable All dimensions in mm...