Firmware V3.15
21.04.2021
363/401
•
•
•
Menu 2-1-3 Zone 1A Altern.
COOLING 1A POS: XXXXX
Entry
Default
Setpoint R4.1 XXX °C
Room air temperature setpoint
-45..30
-24 °C
Hystersis R4.1 X K
Room air temperature hysteresis setpoint
1..8
2 K
HT. Cir. Setp. XXX °C
Heating circuit setpoint, only shown when single-
zone operation is set (Menu 6-1)
--, -45..30
-24 °C
HT. Cir. Hyst. X K
Heating circuit hysteresis setpoint, only shown
when single-zone operation is set (Menu 6-1)
1..8
1 K
Menu 2-1-4 Zone 2A Altern.
COOLING 2A POS: XXXXX
Entry
Default
Setpoint R4.3 XXX °C
Room air temperature setpoint
-45..30
-24 °C
Hystersis R4.3 X K
Room air temperature hysteresis setpoint
1..8
2 K
Menu 2-2 Defrost
DEFROST POS: XXXXX
1 Zone 1
Menu 2-2-1
2 Zone 2
Menu 2-2-2
Only shown when two-zone operation is set (Menu 6-1)
3 Zone 1A Altern.
Menu 2-2-3
Not shown when setpoint toggle is disabled (Menu 3-3)
4 Zone 2A Altern.
Menu 2-2-4
Only shown when two-zone operation is set (Menu 6-1) and setpoint toggle is not
disabled (Menu 3-3)
Содержание UA 400
Страница 26: ...Firmware V3 15 21 04 2021 26 401 Solenoid valve Relay for Solenoid Valve 1...
Страница 133: ...Firmware V3 15 21 04 2021 133 401 Upper case and lower case can be toggled by tapping the MODE button...
Страница 172: ...Firmware V3 15 21 04 2021 172 401 Service Mode 6 7 2 SERVICE MOD...
Страница 244: ...Firmware V3 15 21 04 2021 244 401...
Страница 324: ...Firmware V3 15 21 04 2021 324 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint...
Страница 357: ...Firmware V3 15 21 04 2021 357 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint...
Страница 361: ...Firmware V3 15 21 04 2021 361 401 FANS 2 Pos XXXXX Fan Delay Fan delay...
Страница 372: ...Firmware V3 15 21 04 2021 372 401...
Страница 399: ...Firmware V3 15 21 04 2021 399 401 12 2 Mechanical Data DIN rail mounting A Connector set with cable All dimensions in mm...