Firmware V3.15
21.04.2021
112/401
Mode of operation „positive"
means that operation of the relay is not inverted:
The relay is energized when the controller activates the function output (e.g. cooling = ON).
(This means that the contact of a normally open relay is closed.)
The relay is not energized when the controller deactivates the function output (e.g. cooling = OFF).
(This means that the contact of a normally open relay is open.)
Mode of operation „inverted"
means that operation of the relay is inverted:
The relay is not energized when the controller activates the function output (e.g. alarm = ON).
(This means that the contact of a normally open relay is open.)
The relay is energized when the controller deactivates the function output (e.g. alarm = OFF).
(This means that the contact of a normally open relay is closed.)
* The function for the frame heater / pane heater can be configured via the parameter „
Invert
Output
" (menu 2-5-2 / menu 2-6-2).
Содержание UA 400
Страница 26: ...Firmware V3 15 21 04 2021 26 401 Solenoid valve Relay for Solenoid Valve 1...
Страница 133: ...Firmware V3 15 21 04 2021 133 401 Upper case and lower case can be toggled by tapping the MODE button...
Страница 172: ...Firmware V3 15 21 04 2021 172 401 Service Mode 6 7 2 SERVICE MOD...
Страница 244: ...Firmware V3 15 21 04 2021 244 401...
Страница 324: ...Firmware V3 15 21 04 2021 324 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint...
Страница 357: ...Firmware V3 15 21 04 2021 357 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint...
Страница 361: ...Firmware V3 15 21 04 2021 361 401 FANS 2 Pos XXXXX Fan Delay Fan delay...
Страница 372: ...Firmware V3 15 21 04 2021 372 401...
Страница 399: ...Firmware V3 15 21 04 2021 399 401 12 2 Mechanical Data DIN rail mounting A Connector set with cable All dimensions in mm...