Firmware V3.15
21.04.2021
167/401
•
•
Menu 6-6 - Emergency power operation
NOTNETZ POS: XXXXX
Input
Default
Fkt. Kühl. AUS xxx
Cooling functionality switched off during emergency
power operation? (Y/N)
,
, (Y/N)
N
Fkt. Abt. AUS xxx
Defrost functionality switched off during emergency
power operation? (Y/N)
,
, (Y/N)
N
Fkt. Lüft. AUS xxx
Fans functionality switched off during emergency
power operation? (Y/N)
,
, (Y/N)
N
Fkt. Rhmhg.AUS xxx
Frame heater functionality switched off during
emergency power operation? (Y/N)
,
,(Y/N)
N
Fkt. Licht AUS xxx
Light functionality switched off during the emergency
power operation? (Y/N)
,
, (Y/N)
N
Menu 6-7 Advanced
Erweitert POS: XXXXX
1 SDS TEV
Continue to menu 6-7-1
2 Service Mode
Continue to menu 6-7-2
Содержание UA 400
Страница 26: ...Firmware V3 15 21 04 2021 26 401 Solenoid valve Relay for Solenoid Valve 1...
Страница 133: ...Firmware V3 15 21 04 2021 133 401 Upper case and lower case can be toggled by tapping the MODE button...
Страница 172: ...Firmware V3 15 21 04 2021 172 401 Service Mode 6 7 2 SERVICE MOD...
Страница 244: ...Firmware V3 15 21 04 2021 244 401...
Страница 324: ...Firmware V3 15 21 04 2021 324 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint...
Страница 357: ...Firmware V3 15 21 04 2021 357 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint...
Страница 361: ...Firmware V3 15 21 04 2021 361 401 FANS 2 Pos XXXXX Fan Delay Fan delay...
Страница 372: ...Firmware V3 15 21 04 2021 372 401...
Страница 399: ...Firmware V3 15 21 04 2021 399 401 12 2 Mechanical Data DIN rail mounting A Connector set with cable All dimensions in mm...