Firmware V3.15
21.04.2021
165/401
•
Menu 6-5 Alarm priorities
ALARMPRIOS POS: XXXXX
Input
Default
KühlstellenprioX
Priority of the
alarms can be set
globally using the
refrigeration point
priority (menu
6-1) (Y)
,
, (Y,N)
N
Priorität:XX
Display of
refrigeration point
priority (menu
6-1)
only displayed if
Kühlstellenprio is
set to Y
The following parameters are only displayed if
Kuhlstellenprio is set to N. The possible entries for the
priority of the alarms have the following meanings:
-=Event
is ignored
0=Message (only entry in message list)
1=Alarm
with priority 1
..
99=Alarm with priority 99
Low temp.
Lower alarm
temperature limit
value undercut;
priority is
applicable for all
messages
low-
temp. zone 1,
low-temp. zone 2
-, 0..99
2
High temp
Upper alarm
temperature limit
value exceeded;
priority is
applicable for all
messages
high-
temp. zone 1,
high-temp. zone
2
-, 0..99
1
Sensor fault
Temperature
sensor failed
-, 0..99
2
No Defrost
No defrost within
the alarm delay
time
Priority is
applicable for the
message
No
Defrost
-, 0..99
2
Timer-Term. Defrost
Defrost ended by
safe defrost time
-, 0..99
0
Power failure
Start-up after
power failure
-, 0..99
0
First start
Commissioning of
the controller
(basic settings
loaded!)
-, 0..99
2
Содержание UA 400
Страница 26: ...Firmware V3 15 21 04 2021 26 401 Solenoid valve Relay for Solenoid Valve 1...
Страница 133: ...Firmware V3 15 21 04 2021 133 401 Upper case and lower case can be toggled by tapping the MODE button...
Страница 172: ...Firmware V3 15 21 04 2021 172 401 Service Mode 6 7 2 SERVICE MOD...
Страница 244: ...Firmware V3 15 21 04 2021 244 401...
Страница 324: ...Firmware V3 15 21 04 2021 324 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint...
Страница 357: ...Firmware V3 15 21 04 2021 357 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint...
Страница 361: ...Firmware V3 15 21 04 2021 361 401 FANS 2 Pos XXXXX Fan Delay Fan delay...
Страница 372: ...Firmware V3 15 21 04 2021 372 401...
Страница 399: ...Firmware V3 15 21 04 2021 399 401 12 2 Mechanical Data DIN rail mounting A Connector set with cable All dimensions in mm...