7.14 Wiring of the master-slave function for defrost synchronization
For defrost synchronization via wiring the auxiliary contactors of the master defrost relay are switched in parallel
and then routed as a 230 V signal to the slave's external defrost input (terminals D11/D12). The auxiliary
contactors of the slave controller are also connected in parallel and conducted back as a 230 V level to the
external defrost input of the master. This enables the software to determine whether defrosting is still taking
place in both case controllers.
Basic diagram for wiring between one master and
one
or
more
slave case/cold-room controllers:
Warning - hazardous electrical voltage!
Danger of electric shock! BEFORE and AFTER
connection it must checked that the 230 V AC digital
inputs are off load!
The description and operating instructions for the master-slave mode via wiring are contained
in
chapter
.
Danger of short circuit!
When wiring master and slave case/cold-room controllers, make sure that
power supply is made with only
one
phase (e.g. only through L1, see illustration)!
Defrosting is terminated by the software not later than when the set safe defrost time expires. The
external clock must be wired as a passing contact as it only provides the start signal for the defrosting.
The shutdown is entirely managed by the participating controllers according to their safe defrost time.
Содержание UA 400
Страница 26: ...Firmware V3 15 21 04 2021 26 401 Solenoid valve Relay for Solenoid Valve 1...
Страница 133: ...Firmware V3 15 21 04 2021 133 401 Upper case and lower case can be toggled by tapping the MODE button...
Страница 172: ...Firmware V3 15 21 04 2021 172 401 Service Mode 6 7 2 SERVICE MOD...
Страница 244: ...Firmware V3 15 21 04 2021 244 401...
Страница 324: ...Firmware V3 15 21 04 2021 324 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint...
Страница 357: ...Firmware V3 15 21 04 2021 357 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint...
Страница 361: ...Firmware V3 15 21 04 2021 361 401 FANS 2 Pos XXXXX Fan Delay Fan delay...
Страница 372: ...Firmware V3 15 21 04 2021 372 401...
Страница 399: ...Firmware V3 15 21 04 2021 399 401 12 2 Mechanical Data DIN rail mounting A Connector set with cable All dimensions in mm...