Firmware V3.15
21.04.2021
183/401
•
DERF. TIMER POS: XXXXX
Entry
Default
Defr. 4 xxxxx hh:mm
Defrost start time with internal defrosting;
Weekday, time; shown only when parameter
defrost timer = INT
,
, (Mo-Su etc.) or
numbers (hh:mm)
Mo-Su20:00
...
Defr. 14 xxxxx hh:mm
Menu 3-2-a Def.Tim.Z2
DEFR.TIMER POS: XXXXX
Entry
Default
Defrost Timer XXX
Setting for how temperature zone 2 should
defrost:- MitZ1 Together with zone 1- INT
Internally- EXT Externally – the defrost of both
temperature zones is started simultaneously via
the external signal
,
,
(ViaZ1(ViaZ1,EXT,INT)
ViatZ1
Safe Defr Time XXX m
Safe defrost time, i.e. max. allowed duration of
defrosting (internal defrost only)
0..120
60 min
Manual Defrost XXX
Status (ON/OFF) of auxiliary manual defrost *)
,
, (ON/OFF)
OFF
Defr. 1 xxxxx hh:mm
Defrost start time for internal defrost; weekday,
time of day; shown only when parameter
defrost
timer
= INT
,
, (Mo-Su) or numbers
(hh:mm)
Mo-Su01:00
...
Defr. 14 xxxxx hh:mm
*) Parameter automatically set to ON for safe defrost time at first start.
Содержание UA 400
Страница 26: ...Firmware V3 15 21 04 2021 26 401 Solenoid valve Relay for Solenoid Valve 1...
Страница 133: ...Firmware V3 15 21 04 2021 133 401 Upper case and lower case can be toggled by tapping the MODE button...
Страница 172: ...Firmware V3 15 21 04 2021 172 401 Service Mode 6 7 2 SERVICE MOD...
Страница 244: ...Firmware V3 15 21 04 2021 244 401...
Страница 324: ...Firmware V3 15 21 04 2021 324 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint...
Страница 357: ...Firmware V3 15 21 04 2021 357 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint...
Страница 361: ...Firmware V3 15 21 04 2021 361 401 FANS 2 Pos XXXXX Fan Delay Fan delay...
Страница 372: ...Firmware V3 15 21 04 2021 372 401...
Страница 399: ...Firmware V3 15 21 04 2021 399 401 12 2 Mechanical Data DIN rail mounting A Connector set with cable All dimensions in mm...