Firmware V3.15
21.04.2021
119/401
7.10 Terminal assignment of the 4..20 mA analogue inputs
Connection of pressure transmitters / humidity sensors (only analogue input 2)
Controller type
Terminal No.
Analogue input AIN1
Analogue input AIN2
All controllers
11
+24 V DC
+24 V DC
12
AIN1 (4..20 mA)
sans fonction
–
13
GND
GND
14
–
AIN2 (4..20 mA)
sans fonction
Warning about dangerous electrical voltage!
If mains power is connected to the analogue inputs,
this results in destruction of the controller!
Malfunction due to interference!
All supply lines from and to the case controller must be shielded
(cable type: LiYCY)! If sensor cables are exclusively laid within the refrigerated case to be monitored
and sources of interference (e.g. parallel power lines) are not anticipated, then it is possible to
dispense with shielding. As a general rule, care should be taken to ensure that signal cables and
cables carrying mains voltage are routed in separate cable channels.
Содержание UA 400
Страница 26: ...Firmware V3 15 21 04 2021 26 401 Solenoid valve Relay for Solenoid Valve 1...
Страница 133: ...Firmware V3 15 21 04 2021 133 401 Upper case and lower case can be toggled by tapping the MODE button...
Страница 172: ...Firmware V3 15 21 04 2021 172 401 Service Mode 6 7 2 SERVICE MOD...
Страница 244: ...Firmware V3 15 21 04 2021 244 401...
Страница 324: ...Firmware V3 15 21 04 2021 324 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint...
Страница 357: ...Firmware V3 15 21 04 2021 357 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint...
Страница 361: ...Firmware V3 15 21 04 2021 361 401 FANS 2 Pos XXXXX Fan Delay Fan delay...
Страница 372: ...Firmware V3 15 21 04 2021 372 401...
Страница 399: ...Firmware V3 15 21 04 2021 399 401 12 2 Mechanical Data DIN rail mounting A Connector set with cable All dimensions in mm...