7.8 Terminal assignment of the 24 V DC transistor outputs
Controller type
Transistor output 1:
81: 24 V DC / max. 50 mA
82: OUT
83: GND
Transistor output 2:
91: 24 V DC / max. 50 mA
92: OUT
93: SHIELD
UA 111, UA 111 DUA 121, UA 131, UA 131 LS,
UA 131 DDUR 141 NK, UR 141 TK
Lighting control
(terminals 81/82)
Frame heater
(terminals 91/92)
UA 141
Lighting control
(terminals 81/82)
Control of external devices
(terminals 91/92)
Warning about dangerous electrical voltage!
If mains power is connected to the transistor outputs, this results in destruction of the controller!
Destruction of the transistor outputs!
Due to the maximum capacity of 50 mA of the transistor
outputs, 24 V DC coupling relays must be used for controlling the load.
If any transistor output is activated by the controller, the associated green LED lights; for details see
chapter
. For further details about the function of the outputs, see chapter
Relais- und Transistor-Ausgänge
.
Содержание UA 400
Страница 26: ...Firmware V3 15 21 04 2021 26 401 Solenoid valve Relay for Solenoid Valve 1...
Страница 133: ...Firmware V3 15 21 04 2021 133 401 Upper case and lower case can be toggled by tapping the MODE button...
Страница 172: ...Firmware V3 15 21 04 2021 172 401 Service Mode 6 7 2 SERVICE MOD...
Страница 244: ...Firmware V3 15 21 04 2021 244 401...
Страница 324: ...Firmware V3 15 21 04 2021 324 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint...
Страница 357: ...Firmware V3 15 21 04 2021 357 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint...
Страница 361: ...Firmware V3 15 21 04 2021 361 401 FANS 2 Pos XXXXX Fan Delay Fan delay...
Страница 372: ...Firmware V3 15 21 04 2021 372 401...
Страница 399: ...Firmware V3 15 21 04 2021 399 401 12 2 Mechanical Data DIN rail mounting A Connector set with cable All dimensions in mm...