XDM-300 Installation and
Maintenance Manual
Equipment
Installation
417006-2311-0H3-A00 ECI
Telecom
Ltd.
Proprietary
3-21
9.
If an additional power source (source B) is used, repeat Steps 3 to 8 for
source B.
10.
Route the DC input power cables towards the cable retainers at the rear of
the xRAP-B (see Location of xRAP-B grounding stud (on page
attach them to the retainers with cable ties.
To connect the DC power cable for an XDM-300 shelf:
1.
Before starting, identify the shelf power connectors on the xRAP-B board
in accordance with the following figure.
Figure
3-11: Identification of xRAP-B connectors
2.
Insert the end of the DC power cable terminating with a 5-pin D-type male
connector near the SOURCE A power connectors and connect it to
connector Shelf 1 (see above figure).
3.
Fasten the screws of the D-type connector.
4.
If you are connecting an additional shelf to the xRAP-B, repeat the above
steps for the shelf.
5.
If an additional power source is used, repeat the above steps to connect the
shelves to source B.
6.
Route the DC power cables towards the cable retainers at the rear of the
xRAP-B, and attach them to the retainers with cable ties (see Location of
xRAP-B grounding stud (on page
)).