When a network management station, for example EMS-XDM, is installed on
the site, consider the method of connection to the local network management
station and the maximum allowed distance.
Table
2-1: Equipment dimensions
Equipment type
Height
(mm)
Width
(mm)
Depth
(mm)
Max. weight (kg)
XDM-300
350
443
246
8.2 (shelf only)
30 (fully populated)
TPU 75
443
246
5.5 (shelf only)
10 (fully populated)
XDM-300 + TPU 425
443
246
13.7 (shelves only)
40 (fully populated)
XDM-300 + two
TPUs
500 443 246 21.9 (shelves only)
50 (fully populated)
XDM-300 + two
TPUs + OCU
575 443 246 30.1 (shelves only)
60 (fully populated)
xRAP-100 133 445 185 10
xRAP-B 133 445 185 9.5
xDDF-21 44.5 440 150 3
FST
44.5 440 240 5
ODF
44.5 440 240 8
Power Sources
XDM-300 shelves must be powered only by DC sources complying with the
applicable sections of ETSI 300 132-2 and FTZ 19S1, and the SELV or TNV
requirements of EN 60950. The nominal supply voltage is -48 VDC or
-60 VDC (positive lead grounded); however, the allowed supply voltage range
is -40 VDC to -75 VDC. For redundancy, two separate DC power sources
should be available.
The power consumption of the XDM-300 is:
|
Typical: 1100 W
|
Maximum: 1600 W
N
OTE
:
If the planned power consumption of the equipment
installed in the shelf is 80% or more of the maximum listed
value, it is recommended to consult ECI Telecom’s Customer
Support.