Ensure that the XRGI® system remains in operation and that the area is appropriately heated if you are absent during periods of frost
and/or the winter months.
Components that can cause injury on contact (hot and/or electrically conductive parts) are concealed behind panels that can only be
removed with keys or tools. Only permit authorised EC POWER specialists to remove these panels.
The door on the iQ-Control Panel is there for your protection and should only be opened by trained electricians. The main switch
disconnector (red switch) is located on the left-hand side of the iQ-Control Panel. When it is switched on, there is a risk of you getting
an electric shock if touching any of the control components. The iQ-Control Panel contains sensitive electronic components. If they
are not handled professionally, the XRGI® system may be damaged.
The cover on the Power Unit is there for your protection. In particular, be aware of the following when opening the Power Unit:
■
The engine gets hot. You risk being burned if you touch it or any of the other components.
■
The protective cover conceals parts that start to rotate when the XRGI® system starts up and is running. Touching these parts
while the Power Unit is running can be fatal. Only permit authorised and trained personnel to touch components under the
protective cover when the system is running. Avoid wearing loose-fitting clothing, jewellery and untied long hair when
checking the Power Unit visually, as they could become caught up in rotating parts.
■
The generator and many other parts are connected to the power supply system. Touching non-isolated parts can be fatal.
■
There is a risk of damage to the hearing of anyone in the vicinity of a running Power Unit with an open cover. Please wear
approved hearing protection when the cover is open..
Do not use or store any explosive or easily flammable materials (e.g., petrol, paper, paint) in the vicinity of where the XRGI® system is
installed. Do not use any sprays, solvents, cleaning materials that contain chlorine, paints, adhesives etc. in the vicinity of the XRGI®
system. These materials could present an ignition hazard but could also lead to corrosion – even in the exhaust system.
Check that the supply of combustion air to the XRGI® system is unimpeded. Do not position any equipment with extraction, such
as fans, tumble driers or dehumidifiers, in the vicinity of the XRGI® system without consulting your authorised EC POWER specialist.
Check with your authorised EC POWER specialist to ensure that there is still a sufficient supply of combustion air to the XRGI® system
before fitting moisture-tight windows. The Power Unit‘s combustion air should not contain any solvents or halogen compounds,
which can cause corrosion and damage when the XRGI® system is operated. Halogen compounds are used in industry, trade and
household products.
One option for providing frost protection would be to drain the XRGI® system. It must be ensured that the XRGI® system is completely
drained. Always take the advice of your authorised EC POWER specialist.
3.3.5
F R O S T P R O T E C T I O N
3.3.6 C O N TA C T H A Z A R D
3.3.7 E X P L O S I V E A N D E A S I LY F L A M M A B L E M AT E R I A L S
3.3.8 C O M B U S T I O N A I R S U P P LY
The monitoring systems are only activated when the system‘s master switch is turned to „I“ and the system has not
been isolated from the power supply.
Closed air supply inlets can result in incomplete combustion and a build-up of carbon monoxide, with the possibility
of poisoning.