XRGI
®
- INSTALLATION GUIDE
VERSION 1.0 2018
55
All electrical connections must be downstream of the main meter to be able to use the power-controlled functions, and a reference
meter must be fitted upstream of all electricity consumers. It is essential that you check that the property is suitable before using
power-controlled mode: Major load fluctuations, such as due to machinery or lights, may cause the XRGI® system to cut in and out
frequently, which may reduce its working life and make it more susceptible to malfunctioning.
The iQ-Control Panel is equipped with an automatic disconnection device (mains/system protection) in line with DIN VDE 0126-1-1.
There is therefore no need for a switch point with an isolating function accessible at all times with single units.
E l e c t r i c a l c o n n e c t i o n o n t h e i Q - C o n t r o l P a n e l
The following electrical cables and components are required and are not included in the delivery:
i Q 1 0
Fuse
32A gL
Fuse cable
5 x 10 mm
2
, e.g., NYM-J 5 x 10 mm
2
Generator cable
H07RN-F 4 x 6 mm
2
CEE socket for generator
32A with spring terminals
Potential equalisation
1 x 6 mm
2
, H07V-K
Network cable
SFTP CAT6 RJ45
i Q 1 5
Fuse
63A gL
Fuse cable
5 x 16 mm
2
, e.g., NYM-J 5 x 16 mm
2
Generator cable
H07RN-F 4 x 10 mm
2
CEE socket for generator
63A with spring terminals
Potential equalisation
1 x 6 mm
2
, H07V-K
Network cable
SFTP CAT6 RJ45
i Q 2 0
Fuse
63A gL
Fuse cable
5 x 16 mm
2
, e.g., NYM-J 5 x 16 mm
2
Generator cable
H07RN-F 4 x 10 mm
2
CEE socket for generator
63A with spring terminals
Potential equalisation
1 x 6 mm
2
, H07V-K
Network cable
SFTP CAT6 RJ45
Incorrect installation such as mains supply to the wrong terminals can destroy the electronics and thus cause
equipment damage. Connect only the power supply cable to the terminals marked for this purpose.
Metered consumers
Consumer X
Consumer 2
Consumer 1
Domestic supply connection
Reference
Feed-in
Signal cable
Possible reference meter
for power-controlled or
power-optimised operation
Non-metered consumers
e.g. auxiliary drives, such
as heat pumps or similar.
Mains power supply cable
5 × 16 mm
²
Fig. 5.21 – Electrical connection XRGI® 15/20