XRGI
®
- INSTALLATION GUIDE
VERSION 1.0 2018
48
X R G I® - S E C T I O N
F M - S E C T I O N
B U I L D I N G S E C T I O N
Pipe diameter according to
type of Flow Master
If the entire heating water supply
for the building runs through the
Storage Tank (cf. Hydraulic solution
2HO and 2HM on page 45), design
the pipes to and from the Storage
Tank, as well as the Storage Tank
connections, according to the heat
requirements of the building to be
heated.
Pipe diameter sized according to
heat requirements in the building
to be heated
Pipe diameter sized according
to type and number of XRGI®
F M - S E C T I O N
R E CO M M E N D E D D I A M E T E R
( F P R 10M A N D 5 X 90° B E N D S )
I M P O R TA N T:
X R G I® - S E L E C T I O N
XRGI® type
XRGI® 6
XRGI® 9
XRGI® 15
XRGI® 20
1
DN 25
DN 25
DN 32
DN 32
2
DN 32
DN 32
DN 40
DN 50
3
DN 32
DN 40
DN 50
DN 65
4
DN 40
DN 50
DN 65
DN 65
Number of XRGI®
FM type
FM 50
FM 150
FM 250
FM 350
DN 25
DN 32
DN 40
DN 50
H E AT I N G P I P E D I M E N S I O N S