XRGI
®
- INSTALLATION GUIDE
VERSION 1.0 2018
41
4.5.1
X R G I ® 6 / 9 - S Y S T E M
4.5
REQUIRED MINIMUM CLEARANCES – ASSEMBLY & MAINTENANCE CLEARANCES
Both the installation and assembly of the XRGI® system, as well as the execution of subsequent maintenance and repair work, must
comply with the following minimum clearances or assembly and maintenance clearances.
All dimensions exclude connections. The height specification refers to the upper edge of the components and the Power Unit when
its cover is closed and is stated in mm.
Fig. 4.30 – XRGI® 6/9 - front view
min. 500 mm
min. 500 mm
min. 100 mm
min. 100 mm
min. 235 mm
min. 1.800 mm
min. 730 mm
min. 1.070 mm
min. 180 mm
min. 50 mm
min. 100 mm
Generator cable
max. length 10.000 mm
Flexible hose
max. length 1.500 mm
Fig. 4.31 – XRGI® 6/9 - footprint
min. 500 mm
min. 500 mm
min. 500 mm
min. 1.000 mm
SERVICE AREA
SERVICE AREA
SERVICE AREA
min. 100 mm
min. 100 mm
min. 50 mm
min. 100 mm
min. 500 mm
min. 500 mm
iQ-CONTROL PANEL
Q-HEAT DISTRIBUTOR