CV3100 series and MINI series high performance general purpose inverter instruction manual
6-21
or personnel because of unexpected startup of motor.
P2.17
Failure self-reset times
Factory setting
0
Setting range
0-10
P2.18
Failure self-reset interval
Factory setting
3.0s
Setting range
0.5-25.0s
During running, if the inverter is in fault, it will stop output and show out fault code.
After passing the time defined by P2.18, the inverter will self-reset from the failure
and go on running. The times of failure self-reset is specified by P2.17, if which was
set to 0, there is no self-reset function. Resetting the fault is only by hand pressing key
STOP/RESET.
The inverter do not allow to be self-reset to the failure of overheat of overload
P2.19
Jog running frequency
Factory setting
10.00Hz
Setting range
0.00—50.00Hz
P2.20
Jog accel. time
Determined by inverter type
P2.21
Jog decel. time
Determined by inverter type
Setting range
0.1—3600s
The above parameters specify the jog running parameters correlated, shown as the
following Diagram 6-9:
t1
t2
t3
frequency
time
Diagram 6-9 Jog running parameters