CV3100 series and MINI series high performance general purpose inverter instruction manual
6-45
P6.04
Gain of feedback channel
Factory setting
1.00V
Setting range
0.01—10.00
When the feedback channel and specified channel are not at the same level, it can
adjust the gains of feedback channel signal through this parameter.
P6.05
Polarity of feedback channel
Factory setting
0
Setting range
0
Postive
1
Reserved
0
:
Positive
When the feedback signal is more than PID specified quantity, the inverter is asked to
decrease frequency output, namely minish feedback signal in order to balance PID.
Giving out winding of tension control system and constant pressure water supply
system are all fit for this situation.
Positive action
Close-loop
provision
Speed
Diagram 6-22 Positive charictercharacteristic
P6.06
Proportion gain P
Factory setting
1.00
Setting range
0.01—10.00
P6.07
Integral time Ti
Factory setting
1.00s
Setting range
0.1—200.0s
P6.08
Differential coefficient time Td
Factory setting
0.0s
Setting range
0.0—10.0s