CV3100 series and MINI series high performance general purpose inverter instruction manual
6-3
same. The revised frequency value will be stored into P0.03. Function of UP/DOWN
terminal changing running frequency speed is set by parameter PA.05.
3
:
Digital setting 3
Operating frequency set by frequency commands which are received by RS485
communication port from PC.
4
:
AI1 analog voltage setting
(
0
~
10V
)
Operating frequency set by external terminal AI1
(
0
~
10V
)
, details referred to
P5.00-P5.01.
5
:
AI2 analog current setting
(
0
~
20mA
)
Operating frequency set by external terminal AI2
(
0
~
20mA/0
~
10V
)
, details referred
to P5.02-P5.03
6
:
Pulse signal setting
(
0
~
20kHz
)
Operating frequency set by pulse signal from external terminal DI6
(
0
~
20kHz
)
,
details referred to P5.04-P5.05.
7
:
Compounding setting
Operating frequency set by linearity combination of each setting channel,
compounding mode decided on P5.15-P5.16.
8
:
External terminal selection
Through 8 kinds of on-off combinations of external multi-function terminals to
confirm the frequency input channel. (0 means disconnection of multi-function
terminal and terminal COM, 1 shows multi-function terminal connected with terminal
COM). The function terminals are defined by P4.00-P4.05.
The combinations corresponding to the channels as following:
Channel
terminal 3
Channel
terminal 2
Channel
terminal 1
Frequency setting channel
0
0
0
Keypad potentiometer
0
0
1
Digital setting 1
0
1
0
Digital setting 2
0
1
1
Digital setting 3
1
0
0
AI1 analog signal setting