CV3100 series and MINI series high performance general purpose inverter instruction manual
6-16
frequency
P2.01
time
P2.02
Free running to stop
Stop per deceleration
Without DC braker
startup
Diagram 6-6 Start and stop frequency output curve
P2.03
DC braking current level at starting
Factory setting
0.0%
Setting range
0—100.0%
P2.04
DC braking time at starting
Factory setting
0.0s
Setting range
0.0—30.0s
DC braking current level at starting
:
Brake current percent when the inverter starts
according to DC brake.
DC braking time at starting
:
DC brake current output duration during the inverter
starts.
When DC braking time is 0, the function is invalid; when P2.03, P2.04 are set, the
motor will execute DC brake function first, second start from starting frequency
lasting for the time defined by P2.02, and then accelerate to requested frequency.
Note
:
Only when P0.00=1
,
this group parameters are valid.
P2.05
Accel.&Decel. way
Factory setting
0
Setting range
0
Beeline
1
S-curve
0
:
Beeline acceleration
The inverter frequency output vary by fixed speed, which is linear relationship with
accel & decel time.The most of loads use this way.
1
:
S-curve acceleration or deceleration
During accelerating or decelerating, the inverter frequency output is S-curve
relationship with accel & decel. time, shown as Diagram 6-7. This function is for