CV3100 series and MINI series high performance general purpose inverter instruction manual
6-61
When PWM works under the modulation percentage more than 1, allowable over
modulation enabling can improve the frequency output and torque output. However,
the function can increase voltage harmonic waves output either, resulting in bad
current waves output.
Note
:
When the grid voltage is less than 15% of rated voltage or the situation that the
output torque under variable frequency running is lower than that under industrial
frequency happens( the inverter drives heavy duty for long), this function is allowable
to use.
PA.07
PA.06
Timer value setting
Factory setting
0
Setting range
0
~
65536S
This function is used to set the timing setting, minimum unit setting unit is 1s, when
the setting is 0, it is invalid.
PA.08
PA.06
The Rang of AO1 output
Factory setting
0
Setting range
0
0:0
~
10V/0
~
20mA
1
1: 2
~
10V/4
~
20mA
This function is used to set AO1 output type. 0
~
10V/0
~
20mA and 2
~
10V/4
~
20mA output are optionals.
Note:
The nonstandard edition with Double analog output can realize AO1 and AO2 output
setting separately.
PA.08(FA.08)----AO1/AO2 output range optional
LED single digit--AO1
output range optional:
0----0
~
10V/0
~
20mA
1----2
~
10V/4
~
20mA
LED ten digit--AO2
output range optional:
0----0
~
10V/0
~
20mA
1----2
~
10V/4
~
20mA