CV3100 series and MINI series high performance general purpose inverter instruction manual
6-11
P0.17
V/F Frequency F1
Factory setting
12.50Hz
Setting range
0.00— Frequency F2
P0.18
V/F Voltage V1
Factory setting
25.0%
Setting range
0.0—Voltage V2
P0.19
V/F Frequency F2
Factory setting
25.00Hz
Setting range
Frequency F1—Frequency F3
P0.20
V/F Voltage V2
Factory setting
50.0%
Setting range
Voltage V1—Voltage V3
P0.21
V/F Frequency F3
Factory setting
37.50Hz
Setting range
Frequency F2—Basic operating frequency
P0.22
V/F Voltage V2
Factory setting
75.0%
Setting range
Voltage V2—100.0%
This parameters group is used to expediently set requisite V/F curves.
Diagram 6-5 V/F user-defined curve setting
P0.23
REV/JOG function selection
Factory setting
1
Setting range
0
REV
1
JOG
voltage
frequency
P0.18
P0.20
P0.22
P0.12
P0.21
P0.19
P0.17