CV3100 series and MINI series high performance general purpose inverter instruction manual
5-15
Communication Parameter
Function
Code
Name &
Definition
Set Range
Minimun
Unit
Factory
Default
Communi
cation
Address
Modify
P8.00
Local
communica
tion
address
0
:
Host station
1
~
31: Ancillary station
1
1
0800H
×
P8.01
Communic
ation
scheme
LED single digit
:
Baud rate
selection
1
:
2400BPS
2
:
4800BPS 3
:
9600BPS
4
:
19200BPS 5
:
38400BPS
LED tens digit
:
Data form
0
:
No checkout
1
:
Even checkout
2
:
Odd checkout
LED hundreds digit
:
Reserved
LED thousands digit
:
0
:
return information when modify
data
1
:
no return information when
modify data
1
013
0801H
×
P8.02
Communic
ating
overtime
checkout
time
0.0
~
100.0s
0.1s
10.0s
0802H
×
P8.03
Response
delay
0
~
1000ms
1ms
5ms
0803H
×
P8.04
Linkage
proportion
setting
0.01
~
10.00
0.01
1.00
0804H
○
Protection Function
P9.00
Motor
overload
stall
prevention
factor
30
%~
110
%
1%
105%
0900H
○
P9.01
Low
voltage
prevention
level
360
~
480V(380V machine type)
1V
400V
0901H
○
P9.02
Over
voltage
prevention
level
660
~
760V(380v machine type)
1V
700V
0902H
○
P9.03
Over
current stall
prevention
level
80
%~
220
%
1%
180
%
0903H
○