
CV3100 series and MINI series high performance general purpose inverter instruction manual
6-7
P0.09
Max. Output voltage
Factory setting
380V/220V
Setting range
200V—500V/100V—250V
Max. output voltage correspond to the maximum output voltage when inverter output
basic operation frequency, it is usually motor rated voltage. If under V/F control mode,
adjustment of this parameter can change the output voltage value of inverter; it is
invalid if under SVC mode.
P0.10
Model selection
Factory setting
0
Setting range
0
M type
1
FP type
0
:
M type
Suitable for constant torque loads.
1
:
FP type
Suitable for fan, pump loads, of which output torque and speed are into a relation of
parabola. When inverter is applied for this kind load, power of the inverter can be
increase a level grade.
Note:
Please do not change this parameter optionally, or it will lead to incorrect
display of current and abnormal operation.
P0.11
Torque rising selection
Factory setting
0
Setting range
0
Manual
1
Automatic
It is mainly used to improve the motor torque characteristics at low frequency when
the inverter is under V / F control mode, when the inverter is under vector control
mode, this feature is invalid.
0
:
Manual
Torque rising voltage is specified by P0.12.
1
:
Automatic
Torque rising voltage is direct proportion to the variation of stator current.
When torque rising selection is ―1‖, it can effectively prevent motor which is under
light load from magnetism saturation due to excessive voltage increase, thereby